ReFlex Power™
Mainframe
M380056-01 Rev L
2-13
Figure 2-5. Slot Numbering Assignment, Empty Mainfram Front View
With single-phase service, all input lines are connected in parallel. Effectively, the
three groups of slots (each group comprising four individual slots) are connected
in parallel. However, with three-phase inputs, each line is connected to a
separate group of paralleled slots. Therefore, the physical location of a module in
the Mainframe will determine from which input line the module will draw power.
Balancing of phase currents can be achieved only if the power modules are
installed into the Mainframe so that there is an equal distribution of current
between the three groups of slots, and provided that the same total load is
applied to the set of modules in each group. Refer to Table 2-1 for the power
allocation from the input connector pins to the Mainframe slots.
In multi-Mainframe systems, each Mainframe has an independent AC/DC input.
The interconnect cable that daisy-chains the Mainframes together does not route
input power between assets. Therefore, the input power is not shared among the
assets comprising the system.
Summary of Contents for Elgar ReFlex Power
Page 1: ...M380056 01 Rev L www programmablepower com ReFlex Power Operation Manual...
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...ii This page intentionally left blank...
Page 8: ...iv This page intentionally left blank...
Page 10: ...vi This page intentionally left blank...
Page 21: ...M380056 01 Rev L xvii This page intentionally left blank...
Page 22: ......
Page 85: ...ReFlex Power Controller ReFlex Power 3 22 M380056 01 Rev L This page intentionally left blank...
Page 89: ...AC Power Supplies ReFlex Power 4 4 M380056 01 Rev L Figure 4 1 ACPS Module Front Panel 875VA...
Page 120: ...ReFlex Power AC Power Supplies M380056 01 Rev L 4 35 Figure 4 11 Parallel Output Configuration...
Page 147: ...AC Power Supplies ReFlex Power 4 62 M380056 01 Rev L RST n...
Page 157: ...AC Power Supplies ReFlex Power 4 72 M380056 01 Rev L 26 Reset the unit RST n...
Page 274: ...ReFlex Power DC Power Supplies M380056 01 Rev L 6 71 18 Turn off the output RST n...
Page 275: ...DC Power Supplies ReFlex Power 6 72 M380056 01 Rev L This page intentionally left blank...
Page 279: ...Active Loads ReFlex Power 7 4 M380056 01 Rev L Figure 7 1 LPAL 375W Front Panel...
Page 280: ...ReFlex Power Active Loads M380056 01 Rev L 7 5 Figure 7 2 HPAL 750W Front Panel...
Page 281: ...Active Loads ReFlex Power 7 6 M380056 01 Rev L Figure 7 3 Typical Active Load Rear Panel...
Page 359: ...Active Loads ReFlex Power 7 84 M380056 01 Rev L This page intentionally left blank...