User Manual
© 2022 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com
5
e. Connect Next Gen PCS Filter to Outlet: Plug the Next Gen PCS Filter input power
cord into a properly grounded and compatible branch circuit outlet.
Please Note: Do not plug the Filter into a re-locatable power tap.
i. If the branch circuit outlet is correctly wired and the magnitude of the line
voltage is acceptable (between 105 and 130 V
RMS
for 120V products, or
between 190 and 250V
RMS
for 208-240V products), power will be
connected to the outlets of the Next Gen PCS Filter and the
Green
“System On” LED will illuminate. Your equipment is now protected and
installed correctly. You may now turn all connected equipment back on.
ii. If the branch circuit outlet is incorrectly wired, the
Red
‘Wiring Fault” LED
will illuminate and the LCD Event Monitor will display specific wiring fault
information. If this occurs, contact a licensed electrician to correct the
outlet wiring. Refer to Section:
“Hardware/Next Gen PCS Filter” for LCD
EVENT MONITOR display details.
iii. If neither
“System On”, nor the “Wiring Fault” LED illuminates, there is
either no voltage at the receptacle or the magnitude of the line voltage is
not acceptable (less than 105 V
RMS
or above 130 V
RMS
for 120V products,
or less than 190 V
RMS
or above 250 V
RMS
for 208-240V products). If the
magnitude of the line voltage is not acceptable, specific information will be
displayed on the LCD EVENT MONITOR. If this occurs, contact a licensed
electrician to trouble-shoot the abnormal voltage condition. Refer to
Section:
“Hardware/Next Gen PCS Filter” for LCD EVENT MONITOR
display details.
1. You may also need to verify that the Filter is operating properly.
To test, plug Next Gen PCS Filter into a known properly functioning
outlet. If the
“System On” LED still does not illuminate in the
functioning outlet, contact ESP at 1-800-645-9721.