• To prevent internal UPS temperature rise, and thereby possibly
shortening the effective life of the UPS, keep the air inlets at the
front panel and rear panel of the UPS unobstructed.
Selection of Input and Output Conductors
For the sizing of input/output & battery cabinet connection conductors,
please refer to Table1-1 and Table1-2.
Table 1-1 Cable selection
Model
Current (A)
Input/Output
Phase Conductor
Grounding Conductor Size
(AWG**)
80kVA
96
#1
#6
100kVA
120
#1/0
#6
125kVA
150
#3/0
#6
Table 1-2 Selection for battery cables
Model
Battery
Quantity
Input/Output
Phase Conductor
Grounding Conductor Size
(AWG**)
80kVA
40
225A
4/0
100kVA
40
300A
350 MCM
125kVA
40
350A
500 MCM
*Based on minnimum 75°C conductors, copper only ** based on NEC
Table 250.122 (copper only)