14
A01-00119 Rev. B
Battery Cabinet Installation
1.1.2 Safety Regulations
Do not attempt to dismantle the battery, as its internal electrolyte is
harmful to skin and eyes. When replacing the battery, please adhere to
the following preventive measures to avoid the risk of electric shock and
short-circuit.
• Do not wear watches, rings or other metal jewelry.
• Use insulated tools.
• Do not place tools or metal objects on the battery.
• Keep the battery away from fire. No smoking in vicinity of
batteries.
1.1.3 Installation
CAUTION
The installation and maintenance of the external battery
cabinet(s), should only be performed by factory authorized
service technicians.
The installation steps for the external battery cabinet(s) are as follows.
Step 1 Install the missing cable (removed for shipping) per battery
cabinet manufacturer instructions.
CAUTION
Before making any connections, please make sure main
breaker of the batter cabinet is open.
Step 2 After opening the battery breaker, connect the external battery
cabinet to the UPS using customer supplied conductors in
accordance with all manufacturers recommendations and the
NEC. Use extreme care to ensure proper polarity.