SXRXLXX1 - SIL IntelliPoint RF Series User's Manual
6
After system is installed and level is below the sensing element,
apply power. The RF Series instrument automatically calibrates
and is ready to detect change in level. If properly installed, the
Green LED lights when power is applied. The Red LED should
not be flashing. If the Red LED is flashing, refer to
Section 4:
Troubleshooting.
Cable fittings supplied are weather-resistant.
They are NOT certified as explosion-proof (XP)
or flameproof (d) unless they are specifically
marked.
The IntelliPoint RF instrument is rated Intrinsically
Safe (I.S.) when power is provided from an I.S.
supply.
WARNING:
IntelliPoint RF equipment is rated explosion-proof. When
installing in explosion hazardous areas [rated “potentially
hazardous” (EU) or “hazardous classified” (USA)] observe all
national and local regulations as well as specifications in the
certificate.
Mount sensing element using the following installation
guidelines.
See Figure 2-2.
When installing IntelliPoint RF instrument, ambient
temperature at electronics must not exceed 70°C (158°F).
When installing flange-mounted sensing elements, keep mating
surfaces and bolts free of paint and corrosion to ensure proper
electrical contact with vessel. Avoid using excessive amounts of
Teflon™ tape when installing threaded sensing elements.
Install systems with threaded NPT connection via wrench flats
on the process connection ONLY.
Locate sensing element to avoid enhancing electrostatic
discharge from process medium, as is good practice with any
thermowell, displacer, or sampler. This includes correct bonding
to the tank or silo wall.
If installation area is rated explosion-proof and requires conduit
seal fittings, they should be used in accordance with company
standards and local codes.
2.2
Mounting and Installation Guidelines (Continued)
Summary of Contents for SIL IntelliPoint RF S*R*L Series
Page 4: ...Contents...
Page 6: ...Section 1...
Page 38: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 32 Section 5...
Page 41: ...Specifications 35 Section 6...
Page 43: ...Control Drawings 37 6 1 FM FMc Control Drawings Continued...
Page 44: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 38 6 1 FM FMc Control Drawings Continued...
Page 45: ...Control Drawings 39 6 1 FM FMc Control Drawings Continued...
Page 46: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 40 6 1 FM FMc Control Drawings Continued...
Page 47: ...Control Drawings 41 6 1 FM FMc Control Drawings Continued...
Page 48: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 42 6 1 FM FMc Control Drawings Continued...
Page 56: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 50 6 2 ATEX Control Drawings...
Page 57: ...Control Drawings 51 6 2 ATEX Control Drawings Continued...
Page 66: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 60 6 4 IECEx Control Drawings...
Page 67: ...Control Drawings 61 6 4 IECEx Control Drawings Continued...
Page 75: ...Control Drawings 69 6 5 Mounting and Wiring for Spark Protector Drawings...
Page 77: ...Control Drawings 71 6 5 Mounting and Wiring for Spark Protector Continued...
Page 78: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 72 6 6 Adding a Padded Capacitor...
Page 79: ...Control Drawings 73 6 6 Adding a Padded Capacitor Continued...
Page 80: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 74 6 6 Adding a Padded Capacitor Continued...
Page 81: ...Control Drawings 75 6 7 Dual Seal Assembly for 700 Series Sensing Elements...
Page 82: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 76 6 7 Dual Seal Assembly Continued...
Page 83: ...Control Drawings 77 6 7 Dual Seal Assembly Continued...
Page 84: ...Appendix A...
Page 88: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual A 4 Appendix B...
Page 90: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual B2 EXIDA Report Results...