SXRXLXX1 - SIL IntelliPoint RF Series User's Manual
8
2.3
Input Wiring
WARNING:
If The IntelliPoint instrument is located in a hazardous
environment, do not open the enclosure cover or make/break
any electrical connections without first disconnecting electrical
power at the source. Ensure that the wiring, electrical fittings
and conduit connections conform to electrical codes for the
specific location and hazard level.
The IntelliPoint RF instrument utilizes a universal power supply
and can be operated from any source between 85-250 VAC or 21
to 100 VDC. The universal power supply automatically detects
the input voltage regardless of polarity and does not require
jumper changes. To access, remove the housing lid on the
customer connections side to reveal the Input/Output Module
(IOM). The IOM is an encapsulated assembly that contains
the power supply, outputs and eight wiring terminals. IOM is
held in place with three screws.
See Figure 2-3
.
2.4
Spark Protection
Applications involving insulating granulars and insulating
liquids may produce a static discharge that can damage the
electronics. The RF series instrument is supplied with integral
heavy-duty spark protection to prevent static discharges from
damaging the electronic circuits.
M3 / 2.5mm
Hex Drive
8
7
6
5
4
2
1
3
M3 / 2.5mm
Hex Drive
M5 / Slotted Drive
Ground Connection
#8-32 / Phillips-Slotted
Drive
M4 / 2.5mm Hex Drive
2
3
1
5
6
4
7
8
L2
NO
L1
NC
NO
C
C
NC
85 to 250 VAC
21 to 100 VDC
Auto-Detecting
Relay #1
Relay #2
3
5
6
4
7
8
NO
NC
NO
C
C
NC
3
5
6
4
7
8
NO
NC
NO
C
C
NC
One 5A SPDT Alarm and One 5A SPDT Fault
One 5A DPDT Alarm
Alarm
Fault
Alarm
Alarm
3
5
6
4
7
8
NO
NC
NO
C
C
NC
3
5
6
4
7
8
NO
NC
NO
C
C
NC
One 5A SPDT Alarm and One 5A SPDT Fault
Two 5A SPDT Alarms
Alarm
Fault
Alarm
Alarm
Figure 2-3
Input and Relay Wiring / Customer Connections Side
Summary of Contents for SIL IntelliPoint RF S*R*L Series
Page 4: ...Contents...
Page 6: ...Section 1...
Page 38: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 32 Section 5...
Page 41: ...Specifications 35 Section 6...
Page 43: ...Control Drawings 37 6 1 FM FMc Control Drawings Continued...
Page 44: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 38 6 1 FM FMc Control Drawings Continued...
Page 45: ...Control Drawings 39 6 1 FM FMc Control Drawings Continued...
Page 46: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 40 6 1 FM FMc Control Drawings Continued...
Page 47: ...Control Drawings 41 6 1 FM FMc Control Drawings Continued...
Page 48: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 42 6 1 FM FMc Control Drawings Continued...
Page 56: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 50 6 2 ATEX Control Drawings...
Page 57: ...Control Drawings 51 6 2 ATEX Control Drawings Continued...
Page 66: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 60 6 4 IECEx Control Drawings...
Page 67: ...Control Drawings 61 6 4 IECEx Control Drawings Continued...
Page 75: ...Control Drawings 69 6 5 Mounting and Wiring for Spark Protector Drawings...
Page 77: ...Control Drawings 71 6 5 Mounting and Wiring for Spark Protector Continued...
Page 78: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 72 6 6 Adding a Padded Capacitor...
Page 79: ...Control Drawings 73 6 6 Adding a Padded Capacitor Continued...
Page 80: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 74 6 6 Adding a Padded Capacitor Continued...
Page 81: ...Control Drawings 75 6 7 Dual Seal Assembly for 700 Series Sensing Elements...
Page 82: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 76 6 7 Dual Seal Assembly Continued...
Page 83: ...Control Drawings 77 6 7 Dual Seal Assembly Continued...
Page 84: ...Appendix A...
Page 88: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual A 4 Appendix B...
Page 90: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual B2 EXIDA Report Results...