Installation
11
2.6.5
Manual / Remote Certify™
The "Certify" test feature performs a confidence test of the
system by duplicating the same signal as a high-level alarm
condition without requiring the system to be removed from the
tank. Simulating a high level with the Manual/Remote Certify
feature:
• Checks the AutoVerify™ and system circuits to ensure
proper operation.
• Checks the integrity of the wiring connections.
• Verifies that the sensing element is working properly.
The "Manual Certify" test is initiated with the press of the
Manual Certify Button located on the sensing element / circuit
side of the housing.
The "Remote Certify" test is initiated by creating a momentary
short between contacts 7 and 8 located on the power supply
side of the housing. This can be done with a push button or
relay closure.
After initializing the Certify test, the green LED flashes
for 5 seconds and the red LED will illuminate. The current
moves to the alarm condition for 2 seconds. If the red LED
does not turn on, and the current does not move to the alarm
condition, the Certify has detected a fault.
Consult Section
4: Troubleshooting
.
2.6.6 AutoVerify™
"AutoVerify" is a self-testing function that continuously checks
the system for proper operation when the unit is in the High
Level Failsafe (HLFS) mode and in normal condition.
The Safety IntelliPoint switch is shipped with AutoVerify
Enabled and tamper sealed.
AutoVerify Can Not be Disabled on the Safety IntelliPoint.
If a fault is detected during the AutoVerify cycle, both LEDs
will flash and the relays will de-energize.
Summary of Contents for SIL IntelliPoint RF S*R*L Series
Page 4: ...Contents...
Page 6: ...Section 1...
Page 38: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 32 Section 5...
Page 41: ...Specifications 35 Section 6...
Page 43: ...Control Drawings 37 6 1 FM FMc Control Drawings Continued...
Page 44: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 38 6 1 FM FMc Control Drawings Continued...
Page 45: ...Control Drawings 39 6 1 FM FMc Control Drawings Continued...
Page 46: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 40 6 1 FM FMc Control Drawings Continued...
Page 47: ...Control Drawings 41 6 1 FM FMc Control Drawings Continued...
Page 48: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 42 6 1 FM FMc Control Drawings Continued...
Page 56: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 50 6 2 ATEX Control Drawings...
Page 57: ...Control Drawings 51 6 2 ATEX Control Drawings Continued...
Page 66: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 60 6 4 IECEx Control Drawings...
Page 67: ...Control Drawings 61 6 4 IECEx Control Drawings Continued...
Page 75: ...Control Drawings 69 6 5 Mounting and Wiring for Spark Protector Drawings...
Page 77: ...Control Drawings 71 6 5 Mounting and Wiring for Spark Protector Continued...
Page 78: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 72 6 6 Adding a Padded Capacitor...
Page 79: ...Control Drawings 73 6 6 Adding a Padded Capacitor Continued...
Page 80: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 74 6 6 Adding a Padded Capacitor Continued...
Page 81: ...Control Drawings 75 6 7 Dual Seal Assembly for 700 Series Sensing Elements...
Page 82: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual 76 6 7 Dual Seal Assembly Continued...
Page 83: ...Control Drawings 77 6 7 Dual Seal Assembly Continued...
Page 84: ...Appendix A...
Page 88: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual A 4 Appendix B...
Page 90: ...SXRXLXX1 SIL IntelliPoint RF Series User s Manual B2 EXIDA Report Results...