Overview
DC Asterion Series
3-50
M330460-01 Rev A
The transfer function for the output power will be as follows:
Pout = (I
4-20mA
– 4) (100% rated output power) / 16, with I
4-20mA
in mA
Which sets 0W output power at 4mA and 100% rated power voltage at 20mA.
4-20mA
Source
33
18
PPRG_VSOUR
Figure 3-106. Remote Power Programming Using 4-20mA Source
3.7
Remote Overvoltage Programming
A remote DC voltage source can be connected externally between Pins 5
(OVPRG_VSOUR) and Pin 18 (RTN_PRG) to set the output overvoltage trip level. A
0-10 VDC signal equals 0-110% of rated output voltage. See Figure 3-107 for
connection requirements. This full-scale programming voltage source range can be
set to any value between 2V to 10VDC from front panel. Refer to Section 3.1.8.3.
0-10VDC
VOLTAGE
Source
5
18
OVPRG_VSOUR
Figure 3-107. Remote Overvoltage Programming Using DC Voltage Source
3.8
Remote Output On/Off Control
Remote output on/off control may be accomplished by contact closure, or through an
opto-isolated interface with external voltage sources, AC/DC or TTL/CMOS.
Summary of Contents for Sorensen Asterion AST Series
Page 1: ...M330460 01 Rev A www powerandtest com DC Asterion 1U Operation Manual ...
Page 2: ......
Page 26: ......
Page 53: ...DC Asterion Series Overview M330460 01 Rev A 2 27 This page intentionally left blank ...
Page 54: ......
Page 109: ...DC Asterion Series Overview M330460 01 Rev A 3 55 This page intentionally left blank ...
Page 110: ......
Page 112: ......
Page 117: ...DC Asterion Series Index M330460 01 Rev A 3 ...
Page 118: ...Maintenance DC Asterion Series 4 M330460 01 Rev A This page intentionally left blank ...