Sorensen SGA Series
Operation
M550129-01 Rev AF
3-7
Item
Reference
Functional Description
1
AC Input Connectors
Connection for 3-phase AC.
2
AC Input Safety Ground
Connection for safety ground wire.
3
DC Output Bus Bars
Positive (+) and negative (
–) outputs.
3a HV DC Output Studs
Positive (+) and negative (
–) outputs for 800V and
1000V models only.
4
PAR OUT
Parallel Out connector of master unit for configuring
parallel operation of units when connected to Parallel In
connector of slave unit; see Section 3.11.
5
PAR IN
Parallel In connector of slave unit for configuring parallel
operation of units when connected to Parallel Out
connector of master unit; see Section 3.11.
6
ANALOG CONTROL
Remote Analog Interface connector, J1, for
programming and monitoring signals of output, status
indication, and remote shutdown signals; see Table 3
–5
for individual pin descriptions.
7
SENSE Connector
Input connector, J3, for remote sensing of voltage at the
load to compensate for line drop in load cables; see
Section 3.9.
7a HV SENSE Connector
Input connector,J3, for remote sensing of voltage at the
load to compensate for line drop in load cables, 800V
and 1000V models only; see Section 3.9.
8
RS-232 Connector
†
RS-232 connector for remote digital control.
9
Configuration Switch
†
Eight-position DIP switch to configure the digital
interface of the unit
10 GPIB Connector
†
GPIB connector for remote digital control.
Refer to Figure 3-3, Figure 3-6, and Figure 3-9.
†
Refer to the Programming Manual for details on the digital interface.
Table 3
–3. Rear Panel Connectors and Controls, GPIB Option
Summary of Contents for Sorensen SGA Series DC
Page 1: ...M550129 01 Rev AF www programmablepower com SGA Series DC Power Supplies Operation Manual ...
Page 2: ......
Page 50: ...Installation Sorensen SGA Series 2 30 M550129 01 Rev AF This page intentionally left blank ...
Page 82: ...Operation Sorensen SGA Series 3 32 M550129 01 Rev AF This page intentionally left blank ...
Page 90: ...Installation Sorensen SGA Series 4 8 M550129 01 Rev AF This page intentionally left blank ...
Page 94: ...Maintenance Sorensen SGA Series 5 4 M550129 01 Rev AF This page intentionally left blank ...
Page 97: ...M550129 01 Rev AF Index 3 This page intentionally left blank ...