Local Operation
Using Multiple Supplies
54
Operating Manual for XHR Series Power Supply
Using Multiple Supplies
You can operate power supplies of the same model with outputs in series or in
parallel to obtain increased load voltage or increased current. Split supply operation
gives you two positive outputs or a positive and a negative output.
Note:If your application requires the use of isolated programming inputs, contact the
manufacturer about the optional ISOL interface.
WARNING
There is a shock hazard at the load when using a power supply with a rated
or
combined
output greater than 40 V. To protect personnel against accidental
contact with hazardous voltages created by series connection, ensure that the
load, including connections, has no live parts which are accessible. Also ensure
that the insulation rating of the load wiring and circuitry is greater than or equal to
the maximum output voltage of the power supply.
!
CAUTION
Do not connect power supplies from different manufacturers in parallel or in
series.
!
CAUTION
The remote programming inputs are internally referenced to the power supply’s
negative output. Do not connect remote programming ground lines (J2 terminals
3 and 6) to the supply’s positive output.
Summary of Contents for Sorensen XHR 100-10
Page 2: ......
Page 4: ...This page intentionally left blank ii ...
Page 6: ...This page intentionally left blank iv ...
Page 8: ...This page intentionally left blank vi ...
Page 12: ...List of Figures x Operating Manual for XHR Series Power Supply ...
Page 14: ...List of Tables xii Operating Manual for XHR Series Power Supply ...
Page 47: ...Installation Load Connection 47 Figure 2 9 Multiple Loads with Remote Sensing ...