Interlock Function
M370185-01
3-33
3
Interlock Function
The Interlock function can be used to wire an external shutoff switch that
can be used to enable or disable the power supply output. When the
switch is closed the power supply will operate normally. If the switch is
opened, the power supply will trigger the interlock alarm. The output will
be disabled, the display will blink
In Loc
, and the ALARM LED will
illuminate. This alarm will automatically clear when the switch closes
again, and the output will automatically be restored to its pre-alarm state
(either enabled or disabled). The interlock function can be enabled or
disabled using a SCPI command. Common applications include an
emergency shutoff switch or a door switch.
Connect the switch between pins J3.14 and J3.15 on the AUX Output and
Isolated Analog Programming Connector.
Defining the Interlock Mode
The Interlock mode is controlled via SCPI commands. There is no front
panel access for enabling or disabling the Interlock functionality. See
“Interlock Enable/Disable” on page 5–66.
The SCPI command for setting the Interlock mode to On and Off is:
[:]SENSe[<channel>]:PROTection:INTerlock[:STATe]
Output Protection
The output voltage and the output current can be programmed (preset) to
automatically start at zero Volts and zero Amps upon power-up and upon
output enable. Also, each can be reprogrammed to disable the autotmatic
reset to zero.
Note: With the M10 Option, the power supply voltage output is
preset to 0 Volts.
Programming Voltage Output Preset
To Enable/Disable automatic reset to 0 Volts:
1. Turn the rotary Adjust/Enter control to PRT and press.
2. Turn again until
Pr0 0U7P
is displayed.
3. Press to display
0U7P U0L
.
Summary of Contents for Soresen XTR 100-8.5
Page 2: ......
Page 16: ...xiv ...
Page 28: ...1 8 ...
Page 50: ...Local Operation 3 8 M370185 01 Figure 3 3 Front Panel Menu System ...
Page 93: ...Using Multiple Power Supplies M370185 01 3 51 3 ...
Page 94: ...Local Operation 3 52 M370185 01 ...
Page 128: ...Analog Programming APG and Isolated Analog Programming ISOL 4 34 M370185 01 ...
Page 198: ...Remote Operation 5 70 M370185 01 ...
Page 261: ...SCPI Command Tree M370185 01 A 35 A ...
Page 262: ...A 36 ...
Page 279: ...Index M370185 01 IX 3 described 3 7 3 36 number available 3 36 stored values 3 36 ...
Page 280: ...IX 4 ...