The types of events which may be recorded
are:
•
Triggers
•
Surge Protection Failed
•
Power Outage
•
Network Events
•
Outlet Changes
•
Shutdown Events
•
Firmware Upgrades
Historical Data is a record of measured
electrical parameters, and may be
adjusted to sample certain items at
specific intervals. The available
parameters are:
Historical Parameter
Description
Voltage Max
Line
–
Neutral
The maximum measured RMS voltage between the
conductors during the measurement period.
Neutral
–
Ground
Voltage Min
Line
–
Neutral
The minimum measured RMS voltage between the conductors
during the measurement period.
Neutral
–
Ground
Voltage Average
Line
–
Neutral
The average measured RMS voltage between the conductors
during the measurement period
Neutral
–
Ground
Voltage Peak Max
Line
–
Neutral
The maximum measured peak voltage between the
conductors during the measurement period.
Neutral
–
Ground
Current Max
Total Device
The maximum measured RMS current during the
measurement period.
Current Average
Total Device
The average measured RMS current during the measurement
period.
Current Peak Max
Total Device
The maximum measured peak current during the
measurement period.
Power Max
Total Device
The maximum measured average power during the
measurement period.
Power Average
Total Device
The average measured average power during the
measurement period.
Power Peak Max
Total Device
The maximum measured peak power during the measurement
period.
Frequency Max
The maximum measured Line1-Line2 AC line frequency.
Frequency Min
The minimum measured Line1-Line2 AC line frequency.
Frequency Average
The average measured Line1-Line2 AC line frequency.
Power Factor Mode
Total Device
The most commonly recorded power factor during the
measurement period.
Crest Factor Max
Line Voltage
The maximum crest factor calculated during the measurement
period.
Neutral - Ground Voltage
Current
Crest Factor Min
Line Voltage
The minimum crest factor calculated during the measurement
period.
Neutral - Ground Voltage
Current
Energy Usage
Total Device
The accumulated energy consumed by connected equipment
during the measurement period.