2.3.
Safe Installation
•
Install the filter according to the detailed Installation Instructions provided
with the filter by the manufacturer and according to the description given in
this manual.
•
Make sure to leave enough clearance to enable easy access for safe
maintenance operations.
•
Make sure to have suitable lighting at the filter’s location to enable good
visibility and safe maintenance.
•
Arrange suitable platforms and safety barriers to enable easy and safe access
to the filter without needing to climb on pipes and other equipment. Verify
that any platform, barrier, ladder or other such equipment is built, installed
and used in accordance with the relevant local authorized standards.
•
Check and re-tighten all bolts during commissioning and after the first week
of operation.
•
Use only appropriate standard tools and equipment operated by qualified
operators when installing, operating and maintaining the filter.
•
When installation is required in hazardous environment sites, underground
or high above ground, ensure that the site design and the auxiliary
equipment are appropriate and that installation procedures are carried out in
accordance with the relevant standards and regulations.
•
Ensure walking areas around the installation are slip resistant when wet.
2.4.
Hydraulics
•
We recommend installing manual isolation valves before and after the filter.
•
In order to prevent unexpected water hammer, it is highly recommended to
install a quick pressure release valve.
•
Please note not to accede the maximum working pressure indicated on the
filter’s specifications table
.
•
In cases where the water system is higher than the filters, it is recommended
to install a non-return valve in the filter's downstream.
•
In cases where the water system is lower than the filters, it is recommended
to install a pressure sustaining valve in the filter's downstream.
•
In cases of low working pressure conditions and very poor water quality,
installing a pressure sustaining valve is recommended to maintain efficient
minimal flushing pressure.
•
When the pressure on downstream is over 6 bar during backwash, installing
an orifice valve in the drain manifold is recommended to prevent internal
damage.
Summary of Contents for Spin Klin Nova Angle
Page 8: ...8 Installation Operation Manual Spin Klin Nova 910101 001009 01 2021 Product Overview Single ...
Page 9: ...Installation Operation Manual Spin Klin Nova 910101 001009 01 2021 9 Battery ...
Page 35: ...Installation Operation Manual Spin Klin Nova 910101 001009 01 2021 35 Single On line Battery ...
Page 43: ...Installation Operation Manual Spin Klin Nova 910101 001009 01 2021 43 Battery ...
Page 80: ...80 Installation Operation Manual Spin Klin Nova 910101 001009 01 2021 On line ...
Page 85: ...Installation Operation Manual Spin Klin Nova 910101 001009 01 2021 85 On line ...