Appendix F
Technical Specifications
Supply Voltage:
115 to 220 VAC - 50 to 60 Hz
Current Draw:
1 Amp. Max.
Fuse (1/4 * 1-1/4):
Fast Blow 1 Amp.
Cable Requirements
AVC Display Module to Remote Sensor:
Distance:
Maximum 2,500 feet (750 m)
Cable:
ONLY a #22 gauge stranded, shielded twisted pair cable must be used. (Belden #
8451 or equivalent.) In the presence of any electrical, magnetic, radio
frequencies, wireless or other interference, cable installation MUST be placed in
metallic conduit.
Signal:
30
VDC
- 1.0
Amps.
60
VDC
- 0.3
Amps.
125 VAC
-
0.5 Amps.
AVC Display Module to Master Module
Distance:
Maximum 10,000 feet (3,000 m)
Cable:
Minimum #22 gauge stranded wire (does not have to be shielded, twisted pair)
Signal:
5 VDC, < 5 µA
NOTE:
For Master Alarm, source equipment signal wires must be connected to normally-closed dry contacts. No
electrical voltage can be present and contacts must be closed during normal equipment operation. When
contacts are open; an alarm condition will be activated.