35
www.amico.com
Appendix F
WIRING DIAGRAM:
COMPACT MODULE TO MASTER
NOTE:
Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2).
6" - 8" [0.1m - 0.2 m] #22 gauge
stranded, shielded and twisted
pair cable supplied
Marrette the sensor cable in
a junction box (supplied by
others) to the installation cable
(supplied by others)
#22 gauge stranded,
shielded twisted
pair cable only must
be used, up to a
distance of 2500
ft [750 m]. In the
presence of any
electrical, magnetic
radio, wireless or
other interference,
cable installation
MUST be placed in
a metallic conduit.
Dry contact signal
to Amico Master
Module or BMS
#22 gauge stranded wire