Appendix L
Technical Specifications
Supply Voltage:
115 to 220 VAC - 50 to 60 Hz
Current Draw:
1 Amp Max
Fuse (1/4 * 1-1/4):
Fast Blow 1 Amp
Cable requirement:
Area Display Module to Remote Sensor
Distance:
Maximum 2,500 feet [750 m]
Cable:
Only a #22 gauge stranded, shielded twisted pair cable must be used. (Belden # 8451 or
equivalent). In the presence of any electrical, magnetic, radio frequencies, wireless or other
interference, cable installation MUST be placed in metallic conduit.
Signal:
30 VDC
-
1.0 Amps
60 VDC
-
0.3 Amps
125 VAC
-
0.5 Amps
Master Module to Source equipment:
Distance:
Maximum 10,000 feet [3,000 m]
Cable:
Minimum #22 gauge stranded wire (does not have to be shielded, twisted pair)
Signal:
5 VDC, < 5 µA
Computer Interface Board:
Output:
Dry Contacts NC, open on Alarm
Rating:
30 VDC
-
1.0 Amps
60 VDC
-
0.3 Amps
125 VAC
-
0.5 Amps
CAUTION:
Source equipment signal wires must be connected to normally-closed dry contacts. No electrical
voltage can be present and contacts must be closed during normal equipment operation. When contacts are
open; an alarm condition will be activated.