34 Amico Corporation
TECHNICAL SPECIFICATIONS
Supply Voltage:
115 - 220 VAC, 50 - 60 Hz
Current Draw:
1 Amp. Max.
Fuse (1/4 * 1-1/4):
Fast Blow 1 Amp.
Cable requirement:
LCD Alarm to Remote Sensor:
Important:
Cable:
ONLY a #22 gauge stranded, shielded twisted pair cable must be used. (Belden # 8451
or equivalent.) In the presence of any electrical, magnetic, radio frequencies, wireless or
other interference, cable installation MUST be placed in metallic conduit.
Distance:
Maximum 2000 ft [609.6 m]
Signal:
30 VDC
-
1.0 Amps.
60 VDC
-
0.3 Amps.
125 VAC
-
0.5 Amps.
LCD Alarm to Master:
Distance:
Maximum 10,000 ft [3,000 m]
Cable:
Minimum #22 gauge stranded wire
Signal:
5 VDC
-
< 5 µA
LCD Generic Alarm:
Output:
Dry Contacts NC, open on Alarm
Rating:
30 VDC
-
1.0 Amps.
60 VDC
-
0.3 Amps.
125 VAC
-
0.5 Amps.
Appendix F