MAINTENANCE MANUAL
3.6.15. Battery check
Use isolating switch to disconnect storage batteries.
•
Open the cover.
•
Clean storage battery surface. Check condition of terminals
•
(1). Clean terminals, paint with grease. Open cell plugs of
storage battery (2) to confirm electrolyte level in all cells
reaches 5 ÷ 15 mm (0.2 ÷ 0.6 in) above electrodes or up to
the bottom edge of dipstick in accumulator cells.
Note:
Use glass tube to check the level.
•
Measure the electrolyte density in individual cells with re-
•
fractometer or density meter.
Compare density meter-measured values with the Table.
•
Density
in g/cm
3
in °Be (Beume)
20 °C
68 °F
Tropics
20 °C
68 °F
Tropics
Well recharged
1,28
1,23
32°
27°
Half recharging
1,2
1,12
24°
16°
Discharged, please
recharge
1,12
1,08
16°
11°
Summary of Contents for AP 240
Page 1: ...Book ID 4 P06430CU AP 240 Cummins EN Operating manual...
Page 2: ......
Page 4: ......
Page 5: ...M sto a datum vyd n Place and date of issue Ort und Datum der Ausgabe...
Page 6: ......
Page 14: ...8 AP 240...
Page 15: ...9 AP 240 SPECIFICATION MANUAL 1 SPECIFICATION MANUAL AP 240 Cummins Tier 3...
Page 24: ...18 AP 240 Notes...
Page 25: ...19 AP 240 SPECIFICATION MANUAL Notes...
Page 26: ...20 AP 240...
Page 27: ...21 AP 240 OPERATION MANUAL 2 OPERATION MANUAL AP 240 Cummins Tier 3...
Page 28: ...22 AP 240...
Page 88: ...82 AP 240 Notes...
Page 89: ...83 AP 240 OPERATION MANUAL Notes...
Page 90: ...84 AP 240...
Page 91: ...85 AP 240 MAINTENANCE MANUAL 3 MAINTENANCE MANUAL AP 240 Cummins Tier 3...
Page 92: ...86 AP 240...
Page 156: ...150 AP 240...
Page 166: ...160 AP 240 3 8 Annexes Notes...
Page 167: ...161 AP 240 MAINTENANCE MANUAL Notes...
Page 168: ...162 AP 240 3 8 Annexes Notes...
Page 169: ......