Warnings
Ammonit GmbH / 2005 - 2009
45
5.
Warnings
In the Data Loggers, measurement values are constantly being checked for their
plausibility. As soon as a fault is identified or suspected, the relevant information
is stored. This might involve an anemometer which has not given an impulse
over a longer period of time, or the solar power supply which is not recharging
the battery sufficiently. The warning list can be viewed on the display, and every
fault will be reported by text message to a specified recipient if this option has
been activated in advance with the text message command "W+".
The following measurements are grounds for a "Warning":
•
The external power supply is 5 to
11.8
V
•
The voltage from one of the two batteries is 3 to 6 V
•
The internal temperature is below -35°C or above 8 0°C
•
An anemometer has not given an impulse for the past 12 hours
•
An anemometer has measured a value above 65 m/s
•
A wind-vane has not reported a value for the past 12 hours
•
A wind vane reports the error code "777"
•
A rel. humidity measurement lies outside the range 5 to +110%
•
The temperature measurements lie outside the range –30 to +70°C
•
The air pressure measurement lies outside the range pre-set offset and
1100 hPa
A measurement channel is not checked for plausibility if it has been switched off
(Pre-set slope parameter = "0").
The information in the warning list is stored after the fault has been corrected.
Only when the warning is selected on the display does it examine if this point
can be deleted.
A warning function activated by a text message can be switched off again by the
command message " W- ". Note that the warning function itself is deactivated
once the report has been sent. This prevents a series of reports being sent for
the same fault. The function must therefore be switched back on again once the
cause of the fault has been corrected.
Summary of Contents for METEO-32
Page 35: ...Ammonit Data Logger Manual 34 Ammonit GmbH 2005 2009...
Page 47: ...Ammonit Data Logger Manual 46 Ammonit GmbH 2005 2009...
Page 57: ...Ammonit Data Logger Manual 56 Ammonit GmbH 2005 2009...
Page 73: ...Ammonit Data Logger Manual 72 Ammonit GmbH 2005 2009 4 plug Xtend Plan view Data Logger...