MAN1570-3
3
Installation
Observe anti-static precautions at all times
1.
Two DIP switches are provided, SW2 for addressing (8 way) and SW1 for module options (4 way) as
below.
DIP SW1
Name
Operational Parameters
1
Not used
2 EOL
Zone EOL selection
2 off: EOL = 10uF (default setting)
2 on: EOL = 6K2
3 Ext. Hush Ext. HUSH Input
ON for monitoring the External Hush Input
4 Poll
Poll LED
ON for Poll LED operation
2.
Establish the operational criteria for the module and configure the FACP software accordingly
3.
Remove the white face plate and set the address and operational parameters via the dip switches
4.
All cabling should be run into a general purpose wall box and connected as per
Figure 1
5.
The AM is then screwed to the wall box and tested
–
replace the face plate once testing is complete
Testing
1.
Prepare the most suitable situation for the installation to test the AM
then create a local “alarm”
2.
The alarm indicator should illuminate when the alarm is recognised by the AM
3.
Check the silence function, the configured “Acknowledgement” and “Investigation” timing
4.
Introduce a fault condition eg 1. remove the “Ext. Hush” EOL, 2. check short circuit isolation
operation.