MAN1570-3 

 

 

Installation 

Observe anti-static precautions at all times 

1. 

Two DIP switches are provided, SW2 for addressing (8 way) and SW1 for module options (4 way) as 
below. 

 

DIP SW1 

Name 

Operational Parameters 

Not used 

 

2 EOL  

Zone EOL selection 

2 off:    EOL = 10uF (default setting) 
2 on:    EOL = 6K2 

3 Ext. Hush  Ext. HUSH Input 

ON for monitoring the External Hush Input 

4 Poll 

Poll LED 

ON for Poll LED operation 

 

2. 

Establish the operational criteria for the module and configure the FACP software accordingly 

3. 

Remove the white face plate and set the address and operational parameters via the dip switches 

4. 

All cabling should be run into a general purpose wall box and connected as per 

Figure 1

  

5. 

The AM is then screwed to the wall box and tested 

 replace the face plate once testing is complete 

 

Testing

 

1. 

Prepare the most suitable situation for the installation to test the AM 

then create a local “alarm” 

 

2. 

The alarm indicator should illuminate when the alarm is recognised by the AM 

3. 

Check the silence function, the configured “Acknowledgement” and “Investigation” timing

 

4. 

Introduce a fault condition eg 1. remove the “Ext. Hush” EOL, 2. check short circuit isolation

 

operation. 

 

 

 