Installation Commissioning & Operation
Page 17
7.1
LCD Screen Format
There are 3 events that can be reported and displayed by
SmartTerminal
. The types of event are;
Fire
Faults and
Disables.
The types of events are only associated with sensors and detectors hence faults associated with
modules, loops O/C – S/C, power supplies and so forth are not reported on the LCD.
The
SmartTerminal
has front panel LED’s for each type of event. When
SmartTerminal
is
configured not to report a type of event and that event type is present (and the corresponding front
panel LED is illuminated on the
SmartTerminal
), then a standard information screen is displayed on
the LCD stating the system is not normal and the operator should see the FACP.
Alarm:
If configured the screen format for reporting loop / sensor / zone fire condition is:
Zzzz Alarm
<zone descriptor>
<date> <time> CONTROL*
ZONE FIRE XXX OF XXX DEVICE
►
Fault:
If configured the screen format for reporting loop / sensor / zone fault condition is:
Zzzz FAULT
<zone descriptor>
<date> <time> CONTROL*
FAULT XXX OF XXX DEVICE
►
Note: The fault types only relate to devices.
In the event of a loss of communications, for a period of greater than 15 seconds the
SmartTerminal
will default to the No Communications screen. The format for this screen is:
No Communication
Device Isolate / Disables:
If configured the screen format for reporting loop / sensor / zone disable
condition is:
Zzzz Isolate
<zone descriptor>
<date> <time> CONTROL*
ZONE PRE-ALARM XXX OF XXX DEVICE
►
Pre-alarm:
If configured the screen format for reporting loop / sensor / zone Pre-alarm condition is:
Zzzz PRE-ALARM
<zone descriptor>
<date> <time> CONTROL*
ZONE DISABLED XXX OF XXX DEVICE
►