background image

Europe  

Smart

Terminal

 Installation Commissioning & Operation 

 

Page 18 

Normal / Default: 

The format for reporting that everything is normal is: 

<DATE> <TIME>            ACCESS LEVEL: 1 
<USER DESCRIPTOR LINE 1> 
<USER DESCRIPTOR LINE 2> 
<SYSTEM STATUS>       <DAY MODE-MAN I/O> 
 

The screen is only displayed when there are no alarms, fault or disables on the panel. 

The default screen is only displayed when there are no device alarms, device faults or device 
disables present on the system. The highest priority current system status will be displayed and can 
be one of the following listed in order of highest to lowest priority: 

“SYSTEM ALARM” 

“SYSTEM PRE-ALARM” 

“SYSTEM FAULT” 

“SYSTEM ISOLATE”  

“SYSTEM NORMAL” 

Config: 

The Config screen displays the following 

VX.X (software version number 
Address 
 
               A- A+ C- C+ 

A - A +: adjusts the address 1 to 30, 30 being the maximum number of 

SmartTerminal’s

 that can be 

connected to the FACP, (default is 255 which is not a valid address). 

The function keys perform the following; 

A – Press “Previous”    

A+ press “Next” 

C -   C+: decreases [-] and increases [+] the LCD contrast level. 

The function keys perform the following; 

C – Press “Silence Buzzer” 

 

C+ press “Reset” 

Summary of Contents for SmartTerminal

Page 1: ...IRE DETECTION AND ALARM SYSTEMS SmartTerminal E E EN N N5 5 54 4 4 P P PT T T2 2 2 4 4 4 L L Lo o oo o op p pS S Se e en n ns s se e e Installation Commissioning Operation Our aim is to provide Consistently Excellent Service in the eyes of our customers ...

Page 2: ......

Page 3: ... 2 Fixing the Chassis to the Wall 5 2 1 3 Board Removal Replacement 6 2 1 4 Removing the Knockouts 7 3 Installation Cabling 8 3 1 SmartTerminal Termination Board Interconnection 8 3 2 FACP Comms 8 4 Setting the Address 9 5 Setting the SmartTerminal in LoopMaster 10 6 Operation 12 7 Controls and Indicators 13 7 1 LCD Screen Format 17 8 Specifications 19 9 Trouble Shooting Chart 20 ...

Page 4: ...e status of the FACP is required to be monitored by local personnel and limited control is required Front panel controls that allow the resetting of alarms and activation silencing of alarm devices Enabling operational access to the controls is via a key switch Reports events from devices that are accessible to the host FACP For example if the host FACP is configured with global access then the co...

Page 5: ... e g damp salt air water ingress extremes of temperature abuse etc is at an easily accessible height and such that the indicators are at eye level Typical locations for the panel are the first and most obvious point of contact for emergency services or a security office that is likely to be permanently staffed 2 1 1 Enclosure Details The LCDA can be surface or semi flush mounted is supplied with a...

Page 6: ...e sure that the cable remains connected to at least one board to prevent it being misplaced Push Tab Inwards and Gently Pull the Connector From the Socket Connector Note Care should be taken when detaching this connector as it is necessary to depress the small locking tab to unlock the connector from its base To reconnect the cable the connector must first be correctly aligned then pushed into the...

Page 7: ...TOP AND BOTTOM HINGE PINS OUT OF THE HINGES TAP AROUND RIM TO REMOVE KNOCKOUTS FRONT DOOR KEY SUPPLIED TAPED TO TOP OF ENCLOSURE ENABLE DISABLE KEY SUPPLIED TAPED TO INSIDE OF ENCLOSURE CONTROL PANEL CLIPS INTO FRONT DOOR INSERT KEY TABS HERE TO UNLOCK ENCLOSURE CONNECT BRD82LTB CN1 TO BRD82ICC CN5 BRD82ICC BRD82LTB HINGE PIN 1 HINGE PIN 2 Figure 2 Exploded View BRD82LTB KNOCKOUTS CN1 R 6mm 12 mm ...

Page 8: ...OMMS SGD VE VE A 0V 27V INPUTS MONITORED O PS LOOP 1 LOOP 2 B RS485 RS485 SHD 2 3 4 COM 1 2 AUX OUT2 2 3 4 3 1 4 1 ETH 27V 0V DIAGNOSTICS RS232 RS485 TERM LOAD RESET HLI PORT PWR IN N O C N C N O C N C N O C N C RELAY 1 RELAY 2 RELAY 3 COMMS A B B A B A JTAG JTAG SEL 1 2 3 DIAGNOSTICS CN11 TB1 U2 U1 U4 U3 TB6 R47 R1 CN1 D4 D1 D2 CN10 CN2 CN8 TB4 TB2 TB5 TB3 SW1 D3 K3 R38 R4 R5 R6 R7 10K 10K 10K 10...

Page 9: ...ircuit Board Layout Open the front door locate the CONFIG button situated on the left hand side of the PCB and press for 3 seconds The buzzer and Config LED will double beep and flash respectively to indicate that the Configuration mode has been entered The LCD will now display the Configuration screen This screen consists of the code version number current address and four adjustment markers Thes...

Page 10: ...ght clicking on the SmartTerminal add on parent item from the Tree View opens the menu It contains an option to add a panel Add on to the panel Right clicking on an existing SmartTerminal add on from the Tree View opens the menu It contains an option to add another or remove the current Add on or via the Edit Properties option to open the Add on editing dialog box Note that it is possible to have ...

Page 11: ...s the editing dialog box for that particular SmartTerminal Editing Figure 9 The SmartTerminal add on editing dialog box consists of two types of fields 1 Non editable informational fields Panel The panel number this module belongs to Address The hardware address of this particular module addresses can be in the range of 1 to 30 Reference The reference number of this module 2 Editable fields Multic...

Page 12: ...ed set the address and SmartTerminal should automatically transition to the normal state Should a failure occur on power up press the RESET button located on the LCD PCB see Figure 5 and check the address is correct Normal The Normal state is entered from the Power up or a return from the Fault state and is displayed on the LCD if the SmartTerminal is communicating with the FACP and operating corr...

Page 13: ...ed Enabled Positions Yellow The LED is illuminated when a device has been activated and the device is configured to have a delay before operating the brigade output and alarm devices The LED is turned off when the delay expires and the brigade output and alarm devices are activated or the delay is overridden by the use of the delay override Override When zones and or detectors are configured with ...

Page 14: ...extinguished Active at access level 2 only Red Illuminated when one or more devices are in the pre alarm condition and not disabled Primary Function Press to display the previously displayed LCD screen Secondary Function Set SmartTerminal address A minus decrement number Active at access level 1 and 2 Red Illuminated when the FIRE output is active as a result of a fire condition Primary Function P...

Page 15: ...n for 3 seconds commences a lamp test Lamp test is to test all indicators segments on the LCD and the buzzer Active at access level 1 and 2 Yellow LED is illuminated when there are one or more faults on the system Faults can be Devices missing out of calibration wrong type reporting an internal error Loops short circuit or open circuit Monitored inputs and or outputs on loop devices in fault Monit...

Page 16: ...when the FACP is unable to provide mandatory functions LED is latched until cleared by reset Yellow Illuminated when there is an earth fault detected on the panel Yellow Illuminated steady if any of the alarm devices sounders and or strobes have been disabled and flashes if any of the alarm devices sounders and or strobes are in fault Disable has priority over fault Yellow Illuminated steady if th...

Page 17: ...see the FACP Alarm If configured the screen format for reporting loop sensor zone fire condition is Zzzz Alarm zone descriptor date time CONTROL ZONE FIRE XXX OF XXX DEVICE Fault If configured the screen format for reporting loop sensor zone fault condition is Zzzz FAULT zone descriptor date time CONTROL FAULT XXX OF XXX DEVICE Note The fault types only relate to devices In the event of a loss of ...

Page 18: ...ighest priority current system status will be displayed and can be one of the following listed in order of highest to lowest priority SYSTEM ALARM SYSTEM PRE ALARM SYSTEM FAULT SYSTEM ISOLATE SYSTEM NORMAL Config The Config screen displays the following VX X software version number Address A A C C A A adjusts the address 1 to 30 30 being the maximum number of SmartTerminal s that can be connected ...

Page 19: ...Maximum Current Cabling Requirements Optional 27VDC Power Supply Batteries 27VDC 18VDC 12 4mA back light off buzzer off 43 8mA back light on buzzer on 2 core 1 5 to 2 5mm 1 8A plus 400mA Battery Charging 12Ahr 27VDC OUTPUTS Auxiliary 27VDC Distribution Protection Cabling Requirements 24VDC 500mA Monitored 2 core 1 5 to 2 5mm COMMUNICATIONS Internal to FACP External to FACP Cabling Requirements Fau...

Page 20: ...hort to ground FACP System Fault LED illuminated Ensure correct panel configuration Check all connections for loose wiring FACP Warning System Fault LED illuminated Check correct E O L is fitted Check wiring is connected correctly RS485 Communication Bus not working Refer FACP LCD This may identify where there is a break in the communication line Check the SmartTerminal Diagnostic Config LED is fl...

Page 21: ......

Page 22: ...er England DN3 3GW Tel 44 0 1302 833 522 Fax 44 0 1302 835 021 Email info eu ampac net NEW ZEALAND AMPAC PACIFIC LTD Unit 4 101 Diana Drive Glenfield Auckland New Zealand Tel 64 9 443 8072 Fax 64 9 443 8073 Email info nz ampac net UNCONTROLLED DOCUMENT NOTE Due to AMPAC s commitment to continuous improvement specifications may change without notice HEAD OFFICE Assessed to ISO9001 LPCB ref no 952 A...

Reviews: