Installation & Commissioning of Control & Monitoring Add On’s
Page: 10
4.9
Zone Mimic Indicator Card ( Externally Powered. ) BRD25GIB -C
The externally powered Zone Mimic Indicator Card operates in the same way as does the
internally powered version. The only difference is that the 27 volt power supply is independent of
the FACP. This card would be used when the distance involved causes a significant voltage drop
such that it may effect the reliable operation of the system or the costs involved in the cable is
offset by the availability of a remote 27 volt supply.
Quiescent Current:
13mA ( This current applies to both cards )
Figure 16: PCB Front Layout
Figure 17: Underside of PCB
4.10 LED Annunciator Master ( LAM ) BRD25GIB - E
The LAM provides remote stand alone FACP status, Alarm and Fault / Isolate Indication of 8
zones. Two push buttons, Lamp Test and Silence Buzzer, provide for local testing of the
indicators and buzzer while the buzzer duplicates that at the FACP. A maximum of 4 LAMs with
addresses of 1 to 4 may be cabled to an FACP.
Card & PCB Securing Tabs ( Top & Bottom )
Lettering on slip in
label must be at
least 5mm in height.
Slip In Label
PCB
Alarm
Disable
Fault
Windows for
Slip in Label
FIRE
FAULT
DISABLED
ALARMS STATUS
FIRE OUTPUT STATUS
TEST
DELAY ACTIVE
POWER
LAMP
TEST
SILENCE
BUZZER
FIRE
FAULT / DISABLED
Release of the Clip On Surround
( Metal Cabinet: Push down here and pull out to remove and insert label.
ABS Cabinet: At the top RH cornner of the surround insert the surround removal
tool between it and the front panel then slide along the surround to release)
PWR OUT
PWR IN
+
0V
+24V
COM
-
RS485 OUT TO NEXT LAM
( IF APPLICABLE )
INPUT
MUTE
BUZZER
LK1
TERMINATION LINK
SWITCH
ADDRESS
CN6
ON
1 2
3
4
0V
+24V
+
COM
-
RS485 COMMS IN FROM FACP OR PREVIOUS LAM
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
LAM
4
LAM
3
LAM
2
LAM
1
LINK IS INSERTED ON THE
LAST CARD IN THE CHAIN
LAM 1 - 4
ADDRESS
SETTING
Figure 18: LAM Front Panel and PCB Layout
TB1
SW13
HY1
3V3 Supply
Buzzer BZ1
CN6
0V
+
0V
+
Buzzer
Mute
Input
Address
Switch
EC3AW
RS 485
In
COM
RS 485
Out
-
COM
+
-
+
Termination
Link K2
27V
In
27V
Out
1
2
3 4
ON
+
D17
D18
D19
D20
D1
D2
D3
D4
D5
D6
D7
D8
D9
D10
D11
D12
D13
D14
D15
D16
D21
D22
D23
D24
D25
D26
D27
D28
D29
D30
D31
D32
U1
U2
U3
U4
U5
U6
U7
U8
X1