Installation & Commissioning of Control & Monitoring Add On’s
Page: 21
Step 2
ZONES
CLOCK
OUTPUTS
FIRE FAN
AGENT
SOUNDERS
DISPLAY
########
SET SNDR
BRD O/P
.2..5..8
Z LABELS
MENU
ENTER
LEGEND:
PRESS ENTER TO GO TO SUB MENU, SET MENU OR UPDATE PROGRAM
PRESS MOVE FORWARD THROUGH THE MENU
PRESS MOVE FORWARD / BACKWARD THROUGH THE MENU
CANCEL PRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU
MENU
ENTER
CANCEL
MENU
ENTER
ACF
ISOALTE
ACF
ISOALTE
PRESS ACF TO ISOLATE CIRCUITS EXTERNAL TO FACP
MENU
ENTER
EDIT
TEXT
SET ZONE
T O
ACTIVATE
1...5..8
MENU
ENTER
PROGRAM
MENU
ENTER
MCP ZONE
Z #
1 TO 8
O N
OFF
1 TO 8
IN THIS EXAMPLE SNDR O/P 2,5&8
ARE ACTIVATED BY ZONES 1,5&8
RELAYS
R3 Z-ALRM
1..4...8
R3 SWITCH
.......
R3 Z-FLT
.......
R3 Z-ISOL
.......
R3 I/P
1.3...7.
MENU
ENTER
RELAY 3
MENU
ENTER
SELECT RELAY 3
O N
OFF
MENU
ENTER
UPDATE MENU
MENU
ENTER
IN THIS EXAMPLE RELAY 3 IS ACTIVATED BY ZONES 1,4 OR 8
WHEN IN ALARM OR I/P's 1,3 OR 7 OF THE I/P BOARD ARE ON
TURN OFF
2,3,5,6,7
TURN ON
1,3&7
O N
OFF
MENU
ENTER
UPDATE MENU
MENU
ENTER
TO EDIT DISPLAY
TEXT USE
SELECT
ZONE
MENU
ENTER
TO MOVE THROUGH THE
ALPHABET / NUMBERS
TO MOVE THROUGH
THE WORD
MENU
ENTER
EDIT
TEXT
UPDATE MENU
MENU
ENTER
Programming the Relays and Sounders to be Activated by Zones and Editing Text
CN5
CN10
CN1
CN3
CN2
CN4
Address SW
1 2 3 4
O N
Set to 1
EOL Not Used
RELAY BOARD
MAIN CARD
CN1
CN3
CN2
CN4
Address SW
1 2 3 4
O N
Set to 1
EOL Not Used
INPUT BOARD
CN1
CN2
TB3
Address SW
1 2 3 4
O N
Set to 1
EOL LINK
INSERTED
IN LAST
BOARD OF
THE CHAIN
SOUNDER
BOARD
+
-
+
+
+
+
+
-
-
-
-
-
RS485 and 27V Cabling for the Installation of a Relay, Input and Sounder Board as in the SYSTEM and
PROGRAMMING Menu Structures Above