IntesisBox
®
Modbus Server – Mitsubishi Heavy Industries AC
User’s Manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SL
URL
Email
tel
http://www.intesis.com
info@intesis.com
+34 938047134
12 / 26
Connect to Mitsubishi Heavy Industries Interface
3.1
Use the A-B connector in the right top corner of the front side of the IntesisBox
®
device in
order to connect the Mitsubishi Heavy Industries network (Superlink) to the IntesisBox
®
.
Recommended specifications of the cable for the Superlink are shown as follows:
Size of cable : 0.75 to 1.25 square mm
Max length of wiring : total 1000m (loop wiring is not allowed)
Cable materials :
Twisted Vinyl Cabtyre Cable
VCTF 2 core 0.75 to 1.25 square mm
Twisted Vinyl Cabtyre Cable
VCT 2 core 0.75 to 1.25 square mm
Twisted Vinyl Cable for Control
CVV 2 core 0.75 to 1.25 square mm
Table 3.1
Cable types recommended for Superlink connection
For prevention of electromagnetic noise malfunctions, parallel wiring with the power
line should be avoided
Select the appropriate Superlink mode in the SLK selector. If you are using latest Air
Conditioner of the Mitsubishi Heavy Industries network (New Superlink) select NEW, if not
select OLD.
LEDs placed in the top left corner will show connection status as follows:
LED
Status
IntesisBox
®
behavior
OP
Blinking
Power supply OK
ERR
Off
No error
HOST
Blinking
Internal communication OK
PAC
Blinking
Communication with the Superlink network OK
Table 3.2
IntesisBox
®
LED status information
OP LED behavior must defer depending on the Superlink version, as shown in
Figure 3.3
OP LED blinking behavior depending on
Superlink version
If LEDs (except ERR) are not in the states described above, check section 5.3.
For further information about the Superlink network, look up the Mitsubishi Heavy
Industries Manual or contact your nearest Mitsubishi Heavy Industries supplier.
Connect to Modbus Interface
3.2
3.2.1
Connect to Modbus RTU
Connect the communication cable coming from the Modbus RTU network to IntesisBox
®
). There are 2 existing modes available:
Superlink-II
Superlink-I
On
Off
On
Off
1 sec
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk