background image

 

 

 

 

 

 
 
 

BAT7001 V2 - Power Supply 

 

 

 

 
 
 

Manufactured  in  Australia  by  Ampcontrol 
CSM Pty Ltd ACN 000 915 542  

P:   (02) 4903 4800  
F:   (02) 4903 4888 
E:   

Electronics@ampcontrolgroup.com

  

W:  

Ampcontrolgroup.com

  

No  copies  of  the  information  or  drawings 
within  this  manual  shall  be  made  without 
the prior consent of Ampcontrol. 

 
 
 

USER MANUAL

 

Summary of Contents for BAT7001

Page 1: ...y Ampcontrol CSM Pty Ltd ACN 000 915 542 P 02 4903 4800 F 02 4903 4888 E Electronics ampcontrolgroup com W Ampcontrolgroup com No copies of the information or drawings within this manual shall be made without the prior consent of Ampcontrol USER MANUAL ...

Page 2: ...urpose Ampcontrol further reserves the right to alter the specification of the system and or manual without obligation to notify any person or organisation of these changes Before You Begin We would like to take a moment to thank you for purchasing the BAT7001 Fault driven Power Supply To become completely familiar with this equipment and to ensure correct operation we recommend that you take the ...

Page 3: ...station the substation bus voltage can fall to zero however the current present at the BAT7001 Power Supply s inputs will be several multiples of rated current and is used to ensure that the capacitors remain fully charged It is not generally recommended to use the BAT7001 Power Supply without the presence of upstream voltage transformers This is due to the fact that the BAT7001 Power Supply would...

Page 4: ...than 0 5 Volts after 4 minutes The BAT7001 Power Supply is housed in a standard aluminium flush mounted case see Drawing RELA010 Page 5 for case details 2 1 LED Indication There are two LEDs mounted on the front plate Supply green LED which flashes when an input is present voltage or current or both Output red LED that flashes when the main output DC voltage is healthy 3 Commissioning The followin...

Page 5: ...voltage Iac 0 CT Requirements In 5A 10P25F20 In 1A 10P50F20 not including overcurrent earth fault relays and wiring impedances Example of Designation System 10 P 50 F20 Where 10 10 Composite Error P Class 50 Secondary Voltage F20 Accuracy Limit Factor Outputs Main Voltage Range 48VDC 13000 microfarad capacitor Auxiliary 48VDC 400mA Typical Trip 300 watts Coil Burden Discharge Time 3V after 2 minut...

Page 6: ...BAT7001 Version 2 USER MANUAL ISSUE 1 4 ...

Page 7: ...BAT7001 Version 2 USER MANUAL ISSUE 1 5 ...