BAT7001 Version 2 USER MANUAL ISSUE 1 

-3-

 

4. Equipment List 

144341  BAT7001 Version 2 - 1A Power Supply 
 
144340  BAT7001 Version 2 - 5A Power Supply 
 
144344  BAT7001 Version 2  - Power Supply User Manual 
 

5. Specifications 

Inputs 

Rated Current 

In = 5A 

 

20VA burden at rated current 

 
 

In = 1A 

 

20VA burden at rated current 

 
Rated Voltage 

Vn = 110 VAC 

 

Burden 20VA at rated voltage (Iac = 0) 

 
CT Requirements 

In = 5A, 10P25F20 

 

In = 1A, 10P50F20 

 

(not including overcurrent/earth fault relays and wiring impedances) 

 

 

 

Example of Designation System 

 

10 P 50 F20 

 

Where: 10 = 10% Composite Error 

 

 

P = Class 

 

 

50 = Secondary Voltage 

 

 

F20 = Accuracy Limit Factor 

Outputs 

Main 

Voltage Range 48VDC 

 

13000 microfarad capacitor 

 
Auxiliary 

48VDC, 400mA 

 
Typical Trip 

< 300 watts 

Coil Burden 

Discharge Time 

 

<3V after 2 minutes, <0.5V after 4 minutes 

LED Indication 

Supply 

Green LED flashes when input is present 

Output 

Red LED flashes when main voltage output is healthy 

Summary of Contents for BAT7001

Page 1: ...y Ampcontrol CSM Pty Ltd ACN 000 915 542 P 02 4903 4800 F 02 4903 4888 E Electronics ampcontrolgroup com W Ampcontrolgroup com No copies of the information or drawings within this manual shall be made without the prior consent of Ampcontrol USER MANUAL ...

Page 2: ...urpose Ampcontrol further reserves the right to alter the specification of the system and or manual without obligation to notify any person or organisation of these changes Before You Begin We would like to take a moment to thank you for purchasing the BAT7001 Fault driven Power Supply To become completely familiar with this equipment and to ensure correct operation we recommend that you take the ...

Page 3: ...station the substation bus voltage can fall to zero however the current present at the BAT7001 Power Supply s inputs will be several multiples of rated current and is used to ensure that the capacitors remain fully charged It is not generally recommended to use the BAT7001 Power Supply without the presence of upstream voltage transformers This is due to the fact that the BAT7001 Power Supply would...

Page 4: ...than 0 5 Volts after 4 minutes The BAT7001 Power Supply is housed in a standard aluminium flush mounted case see Drawing RELA010 Page 5 for case details 2 1 LED Indication There are two LEDs mounted on the front plate Supply green LED which flashes when an input is present voltage or current or both Output red LED that flashes when the main output DC voltage is healthy 3 Commissioning The followin...

Page 5: ...voltage Iac 0 CT Requirements In 5A 10P25F20 In 1A 10P50F20 not including overcurrent earth fault relays and wiring impedances Example of Designation System 10 P 50 F20 Where 10 10 Composite Error P Class 50 Secondary Voltage F20 Accuracy Limit Factor Outputs Main Voltage Range 48VDC 13000 microfarad capacitor Auxiliary 48VDC 400mA Typical Trip 300 watts Coil Burden Discharge Time 3V after 2 minut...

Page 6: ...BAT7001 Version 2 USER MANUAL ISSUE 1 4 ...

Page 7: ...BAT7001 Version 2 USER MANUAL ISSUE 1 5 ...

Reviews: