ISUPS2B004 Rev 1
Page 13 of 70
Ampcontrol Pty Ltd
– ABN 28 000 915 542
ISUPS 300Wh V2 USER MANUAL
ISUPS2B004 R2
– DEC/17
4.2 Mandatory Installation Practices
The following information must be adhered to when installing the ISUPS. Failure to adhere to this
information may give rise to unsafe operation.
Using the ISUPS in a manner that exceeds its electrical, functional or physical specifications, or in a way
that is contrary to its operating restrictions, may create risks to personnel and/or equipment resulting in
injury or death.
The ISUPS must be powered within the specified voltage range.
The Conditions of Safe Use listed in the certification must be adhered to.
The installation of the ISUPS must be carried out by suitably trained and qualified personnel.
Identification labels fixed to the ISUPS must not be damaged, removed or covered before, during
or after installation.
The installation is to be in accordance with the relevant installation Standards/Codes of Practice.
Modifications must not be made to any part of the ISUPS. As supplied, the unit is built to, and
complies with the relevant standards. Modifications to its construction will render the unit non-
compliant.
Complete and accurate records of the installation must be kept as part of the site installation.
4.3 Conditions of Use
There are eighteen models of ISUPS with a range of voltage and current limits that may be selected from
Table 1, following. Various output options and battery capacities that are not shown in the table can be
manufactured on request as a system special.
NOTE
System specials will require longer lead times to manufacture.
NOTE
Some standard models of ISUPS have been tested with two different
sets of I.S. parameters. The installer may select and apply only one set
of parameters to the I.S. assessment, depending on the requirements of
the system.
WARNING!
Um = 250V (mains power input) must not be applied when installed in
Zone 0 areas.