11.5 Programmable Relay Outputs (K2, K3 & K4) (Item 11)
The PF1 has three output relays (K2, K3 & K4) with functionality that can be customised using the Smart
Tools software.
The relays can be programmed to have a default state of open (de-energised) or closed (energised).
This will be the state of the output relay when none of the selected parameters are true.
NOTE
Although the K2, K3 & K4 output relays can be set to a default state of
closed (energised), it is important to note that
when the PF1 loses
power all output relays will open (de-energise).
Each of the three programmable outputs relays can be individually programmed to operate under any
combination of the following system states:
Pump running
Pump iSet required
Pump sleeping
Pump stopped
Fan running
Fan stopped
Earth leakage tripped
Earth leakage healthy
Earth continuity tripped
Earth continuity healthy
As a result of enabling this level of flexibility, it is possible to select an invalid combination of states.
It is the responsibility of the user to ensure that any chosen combinations are logical.
The Programmable Relay Outputs can also allow the PF1 to be configured in an Auto/Manual Mode.
This allows the operators to switch between Auto and Manual pump control in the field, without needing
to change the PF1 configuration each time. For more information, refer to Section 6.2.