13
SPECIFICATIONS
General
Compliance
(AS/NZS 2081:2011)
Supply
Regulated Voltage
18 to 28.8Vdc or, 18 to 28.8Vac 50 to 60Hz
Impulse Voltage (max)
50V peak for 200ms
Power Consumption
10VA
Relay Contacts
Contact Rating
110Vac / 30Vdc 1A (Resistive)
Pump & Fan
Toroid
CT 1000/1 50mm PFCT SRS27
Toroid Ratio
1000 : 1
Primary Input Current
1 to 200A
Toroid Window Size
50mm Inner Diameter
S1/2 cable loop
resistance (max)
0.1
Ω
S1/2 length (max)
10m
S1/2 cable type
Twisted pair + shield to Earth (on PF1 end only)
Earth Leakage
Trip Times
50 to 500ms
Trip Levels
30 to 1000mA
Toroid
EL500/60
Toroid Ratio
100 : 1
Toroid Window Size
60mm Inner Diameter
Passband
Wide Band Mode: 30 to 500Hz
50Hz Mode: 30 to 90Hz
S1/2 cable loop
resistance (max)
0.1
Ω
S1/2 length (max)
10m
S1/2 cable type
Twisted pair + shield to Earth (on PF1 end only)
TEST1/2 cable loop
resistance (max)
2
Ω
TEST1/2 length (max)
10m
TEST1/2 cable type
Twisted pair
Earth Continuity
Trip Times
50 to 500ms
Trip Levels (Series)
10 to 45Ω
Trip Levels (Shunt)
1250Ω
Pilot Output Signal
Voltage
<30Vdc
Pilot Cable
C
max
= 0.25µF
L
max
= 0.70mH
Terminating Diode
1N5404 3A
Remote Start Resistor
100R 1% 5W