1.2 Summary of Essential Cautions and Warnings
This sub-section provides a summary of all of the essential caution and warning statements throughout
this document. A reference is also provided to the location within the document.
Section
WARNING!
The PF1 has been design to provide the user with the maximum
flexibility, with regards to configuration. The user is able to
configure the PF1 such that the Earth Leakage and Earth
Continuity protection functions are disabled.
Ampcontrol accepts no responsibility or liability in cases
where the user has incorrectly configured the PF1.
The user
remains ultimately responsible for the configuration of the PF1
and their greater system.
Section
CAUTION!
Overloading any of the output relay contacts can damage the
PF1, potentially resulting in unsafe operation
. The installer is
to ensure that the limitations detailed in the Specifications Table
(Section 13) are respected.
Section
NOTE
Although the EC Pilot terminal (20) is only required to be wired in
if the PF1 relay’s earth continuity protection is to be enabled,
the EC Earth terminal (21) must always be connected
. Failure
to connect the EC Earth terminal to earth will result in non-
compliance.
Section
WARNING!
In Earth Continuity Only Mode, if
remote start is not enabled
,
when the pilot resistance returns to a healthy range (remote stop
button released) the
K1 output relay will energise
.
Section
NOTE
When the Pump configuration is changed, the
iSet parameter
stored in the PF1 will be reset to infinity
. The user will be
required to perform the iSet procedure.
Section
WARNING!
If the PF1 is set to resume after a power failure, the pump can
and will energise after a power outage. All operators should be
aware of this.
This setting should be used with caution.
Section
NOTE
The Facia Stop button will only open the K1 output relay if the
PF1 is set to Pump Mode or Fan Mode. If the PF1 is not set to
either Pump Mode or Fan Mode, the
Fascia Stop button will not
perform a function
.