EL LED (Item 5)
The EL LED is a green LED that has the following operating logic:
Table 20: EL LED Operating Logic
EL LED
Green LED
Earth leakage protection off
Off
Earth leakage healthy
On
Earth leakage trip
1 Flash
Earth leakage toroid trip
2 Flash
EC LED (Item 6)
The EC LED is a green LED that has the following operating logic:
Table 21: EC LED Operating Logic
EC LED
Green LED
Earth continuity protection off
Off
Earth continuity healthy
On
Earth continuity open circuit trip
1 Flash
Earth continuity short circuit trip
2 Flash
EC start button trip
3 Flash
Healthy / Trip LED (Item 7)
The Healthy / Trip LED is a green / red (dual) colour LED that has the following operating logic:
Table 22: Healthy / Trip LED Operating Logic
Healthy / Trip LED
LED Colour
All protection functions are healthy
Green
EL and EC functions both disabled
Off
Earth leakage trip
Red
Earth continuity trip
Red
11.2 Fascia Stop Pushbutton (Item 8)
The PF1 has a Stop pushbutton mounted on its fascia. Pressing the Stop pushbutton will open the K1
output relay, hence opening the outlet’s contactor.
The fascia Stop pushbutton can be used as an alternative to the “Stop” digital input.
NOTE
The Facia Stop button will only open the K1 output relay if the PF1 is
set to Pump Mode or Fan Mode. If the PF1 is not set to either Pump
Mode or Fan Mode, the
Fascia Stop button will not perform a
function
.
11.3 Digital Inputs (Reset, Start & Stop) (Item 9)
The PF1 has three digital inputs that perform pre-programmed functions when they are shorted to the
VDC terminal (for wiring details see Figure 4.4).
Reset Input
Closing the Reset input will clear any latched faults in the PF1, provided that fault conditions no longer
exist.