Start Input
If the outlet is stopped and no fault conditions exist, closing the Start input will initiate the outlet starting
process.
If the outlet is in Pump mode, has just been started, and is within the allowable iSet timeframe, closing
the start input (again) will save the iSet level. For a detailed explanation on the iSet procedure, refer to
Section 6.1.3.
Stop Input
Opening the Stop input, will stop the outlet if it is running.
NOTE
The Start and Stop digital inputs
will not function if neither the Pump
Mode nor the Fan Mode is selected
. If the PF1 is operating as an EL
and/or EC relay only, the function of the K1 output relay will depend
solely upon the health of those protection functions.
11.4 Programmable Digital Input (PI) (Item 10)
The PF1 relay has been implemented with an input that can be configured in the Smart Tools software to
perform different functions. In the initial release of the PF1, this input can be configured as:
Table 23: Programmable Input (PI) Configuration Options
Function
Description
None
The input is disabled and the PF1 relay will not perform
any actions when this input changes state.
Filtered Stop
This input acts as a filtered stop input to the PF1 relay.
When this input is activated, the PF1 will activate an
outlet STOP after the configurable filtering time has
expired. See Section 11.4.1.