High-Current
Demarcation Panel
5
ALERT! Only qualified personnel may install and maintain this product. Verify that all connections meet
requirements specified in local electric codes or operating company guidelines before supplying power.
1.3 Specifications
Inputs/Outputs:
Specification:
Max. fuse rating (each)
100A: Circuit breaker
125A: TFD holder
Max. total load rating of panel
320A: Circuit breaker
400A: TFD holder
Voltage range
±
20 to
±
28 VDC
-40 to -60 VDC
BATT & RTN wire size
#8 to #1 AWG recommended (see note below)
Ground wire size
#10 to #2 AWG recommended (see note below)
Terminal stud sizes
(Input, output and earth ground)
1/4"-20 dual studs on 5/8" centers
Maximum lug width: 0.61-inches
Power dissipation
17W per channel
Short-circuit withstand rating
5000A
Alarms:
Specification:
Alarm relay contacts
0.6A @ 60 VDC
Alarm card power rating
1W
Alarm wire size
Solid: #26 to #22 AWG
Dimensions:
Specification:
Nominal, without brackets:*
Width:
Height:
Depth:
17.25" (43.8 cm)
1.75" (4.4 cm)
10.4" (26.4 cm)
Weight:
Specification:
Weight, shipping
~11 lbs. (~4.5 kg): 009-7001-0104B
~12 lbs. (~5 kg): 009-7001-0104B-TFD
Environment:
Specification:
Operating temperature
-5°C (23°F) to 55°C (131°F)
NOTE:
Wire sizes are recommended based on generally available lug sizes. Ensure wire sizes meet amperage
requirements per NEC.