20
DC+AC Current
(AMP-220 and AMP-320 only)
Range
Accuracy
1) 2)
60.00 A
3)
, 600.0 A
± (2.2 % + 7 LSD) @ DC, 50 Hz to 100 Hz
60.00 A
3)
, 600.0 A
± (2.7 % + 7 LSD) @ 100 Hz to 400 Hz
1) Induced error from adjacent current-carrying conductor: < 0.01 A/A
2) Specified with DC-zero mode applied to offset the non-zero residual
readings, if any
3) Add 10 LSD to the specified accuracy @ < 9 A
Frequency Hz
Function
Sensitivity
1)
(Sine rms)
Range
600 V
50 V
5.00 Hz to 999.9 Hz
60 A (Precise low current)
40 A
50.00 Hz to 400.0 Hz
60 A, 600 A
40 A
50.00 Hz to 400.0 Hz
Accuracy:
± (1.0 % + 5 LSD)
1)
DC-bias, if any, not more than 50% of Sine rms
&
3-Phase Rotation
measurement:
Voltage Range:
65 V to 600 V (sine wave only)
Frequency Range:
35 Hz to 400 Hz
measurement:
Voltage Range:
0.4 V to 600 V (sine wave only)
Frequency Range:
3 Hz to 400 Hz
Voltage Detection (NCV)
Typical Voltage
Bar-graph Indication
20 V (tolerance: 10 V to 36 V)
-
55 V (tolerance: 23 V to 83 V)
- -
110 V (tolerance: 59 V to 165 V)
- - -
220 V (tolerance: 124 V to 330 V)
- - - -
440 V (tolerance: 250 V to 600 V)
- - - - -
Indication:
bar-graph segments and audible beep tones proportional to the
field strength
Detection frequency:
50/60 Hz
Detection antenna:
inside the top side of the stationary jaw