background image

Description

Standard Construction

Shell

Steel

Bladder

Heavy Duty Butyl 
NSF/ANSI 61

Bladder Thickness

.100 Minimum

System Connection Steel - ANSI Flange

Coating

Red Oxide Primer

Factory Precharge

25 PSIG (1.7 bar)

Use:

SG  =  Specific gravity of fluid: 

Water 1 

 

   

Ethylene glycol 1.1 

 

   

Propylene glycol 1.1 

 

   

Glycerin 1.3

Qs  =  Fire pump flow rate in gpm

Qss =  Fire pump flow rate in feet per second

=  Length of pipe in feet

=  Speed of pressure wave 

 

  in feet per second: 

Steel pipe 4500 ft/sec 

 

   

Cast iron = 4500 ft/sec 

 

   

Ductile iron 4500 ft/sec 

 

   

PVC pipe = 1250 ft/sec

P

2

  =  Maximum allowable pressure

P

1

  =  Tank pre-charge pressure setting

=  Gas constant (pre-charge gas) dry air 1.2

 

   

       nitrogen 1.4

A  =  Area of Pipe - pipe size

=  Velocity of water in feet per second

Precise Sizing For Pump Start-up:

Volume of Tank in Cubic Feet  =

SG x 2 x Qs x L

 ) ( 

P

2

 + 14.7

 )

1

/n 

 

 

449a  

      P

1  

+ 14.7 

 

 

 

P

2

 + 14.7

 )

1

/n

 

 

 

    P

1  

+ 14.7

 

 

 

-1

NOTE: Set pre-charge pressure 15% below static pressure.
NOTE: To convert cubic feet to gallons multiply by 7.481.

SIZING THE 

SURGE-TROL

 

              Tank                       A 

                 B   

Sys. 

E            Ship 

 

              Vol.                       Height                  Diameter 

Conn.  Conn.  Conn.  Stand           Wt. 

  Model 

 

 

 

 

 

 

 

Inset CtrLine  Dia 

 

No. 

Lit. 

Gal 

mm 

ins. 

mm 

ins. 

ins. 

ins.  ins. 

ins. 

kg 

lbs.

  SPT-7  200 

53  1245  48

7

/

8

 

610 

24 

1

9

/

16

  8

3

/

16

  19  166  367

 SPT-11  300 

80  1600  62

7

/

8

 

610 

24 

1

9

/

16

  8

3

/

16

  19  208  459

 SPT-14  400  106  1956  76

7

/

8

 

610 

24 

1

9

/

16

  8

3

/

16

  19  282  618

 SPT-18  500  132  2311  90

7

/

8

 

610 

24 

1

9

/

16

  8

3

/

16

  19  333  731

 SPT-21  600  158  1893  74

11

/

16

  762 

30 

1

3

/

8

  7

1

/

4

  24  433  950

 SPT-28  800  211  2365  93

1

/

8

 

762 

30 

1

3

/

8

  7

1

/

4

  24  513  1125

 SPT-35  1000  264  2086  82

1

/

8

 

914 

36 

3

1

/

4

  7

1

/

2

  30  693  1520

 SPT-42  1200  317  2465  94

1

/

2

 

914 

36 

3

1

/

4

  7

1

/

2

  30  784  1720

 SPT-50  1400  370  2781  109

1

/

2

  914 

36 

3

1

/

4

  7

1

/

2

  30  866  1900

 SPT-56  1600  422  2178  85

3

/

4

  1220  48 

1

3

/

4

  10

7

/

8

  42  1049  2300

 SPT-70  2000  528  2528  99

5

/

8

  1220  48 

1

3

/

4

  10

7

/

8

  42  1231  2700

Precise Sizing For Pump Shut-down:

Volume of Tank in Gallons =   Vv 

 

 

 

AF

AF - Acceptance Factor = 

1 - 

P

1

 + 14.7

)

1

/n

 

 

 

 

         P

2  

+ 14.7

Vv - Vacuum Volume  =   Qss x Tc x 7.481

Tc - Critical Time in seconds =  

2L

 

 

 

 

    a

NOTE: Set pre-charge pressure 50% below 

static pressure.

Precise Sizing Example 
For Pump Shut-down Based On:

Pump = 100 GPM
Pipe = 2” Steel Pipe; 1000 ft of pipe
Static Pressure = 100 psig
Max. Pressure = 150 psig
Pre-charge Gas = Dry Air

Tc  =  

2L  =  2(1000)  =  2000   =  .444

 

 

   a          4500        4500

Vv  =  Qss x Tc x 7.481  =  9.5 x .444 x 7.481  =  31.55

AF  = 

1 - 

P

1

 + 14.7

)

1

/n  = 

1 - 

64.7  

)

1

/

1.2

   =  .54

 

 

 

         P

2  

+ 14.7    

        164.7

Volume of Tank in Gallons =   Vv     =  31.55  =  58.4 

 

 

 

AF 

.54

Recommendation = SPT-11

Summary of Contents for SURGE-TROL SPT-11

Page 1: ...L VOID THE PRODUCT WARRANTY THIS PRODUCT MUST BE INSTALLED BY A QUALIFIED PROFESSIONAL FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS IN THE ABSENCE OF SUCH CODES FOLLOW THE CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE AS APPLICABLE West Warwick Rhode Island 02893 INSTALLATION OPERATION INSTRUCTIONS SURGE TROL Surge Arrestor SPT 7 thru SPT 70 MARK OF THE O...

Page 2: ...ments required at the time of initial installation especially if Product is corroded damaged or with diminished integrity Adjustments to pre charge must be done at ambient temperature only Failure to properly size the Product or follow these instructions may result in excessive strain on the system leading to Product failure serious or fatal personal injury leakage and or property damage This Prod...

Page 3: ...it Gal mm ins mm ins ins ins ins ins kg lbs SPT 7 200 53 1245 487 8 610 24 4 19 16 83 16 19 166 367 SPT 11 300 80 1600 627 8 610 24 4 19 16 83 16 19 208 459 SPT 14 400 106 1956 767 8 610 24 4 19 16 83 16 19 282 618 SPT 18 500 132 2311 907 8 610 24 4 19 16 83 16 19 333 731 SPT 21 600 158 1893 7411 16 762 30 4 13 8 71 4 24 433 950 SPT 28 800 211 2365 931 8 762 30 4 13 8 71 4 24 513 1125 SPT 35 1000 ...

Page 4: ...IES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE SPECIFICALLY DISCLAIMED Some states do not allow limitations on how long an implied Warranty lasts so the above limitation may not apply to you Limitations of Remedies THE REMEDIES CONTAINED IN THIS WARRANTY ARE THE PURCHASER S OR FIRST USER S EXCLUSIVE REMEDIES IN NO CIRCUMSTANCES WILL AMTROL BE LIABL...

Reviews: