18
AMW 12_00
O
O
U
U
T
T
D
D
O
O
O
O
R
R
C
C
O
O
N
N
D
D
E
E
N
N
S
S
E
E
R
R
GENERAL
To be used when a swimming pool condenser offers no solution to the problem of excessive heat discharge.
COMPOSITION
several rows of copper pipes (3/8”), with pressed-on aluminium plates, in a housing of galvanized steel plate,
epoxy varnished.
one fan, speed controlled by a pressure triode.
Liquid receiver adapted to the larger quantity of present gas
Pipes are adapted for connection of the outdoor condenser and are extra provided with non-return valves.
A/N outdoor condenser with one (NO) magnetic valve on the swimming pool condenser and one (NC) on the
outdoor condenser.
TECHNICAL DATES
Type of unit
65
92M
140-42M
Condenser
Type
WA15
Number
1
1
1
Output (1)
W
9610
9610
11500
Fan
Air flow
m³/h
3500
Number x
∅
mm
1 x 500
Tension
230V/1/50Hz
Output
W
135
Current
A/ph
0,6
Noise level
DBA (2)
36
Net weight
kg
36
Dimensions
L
mm
730
D
mm
873
H
mm
714
(1)
Capacities are given in Watt for
Δt= 15K
(2)
Sound pressure level at 10 m (+6dB at 5m) in a free field (semi reverberant field)
CONTROL
ELECTRICAL CONNECTIONS/ SEE DIAGRAM
Via a maximum thermostat
at excess temperature the unit control will be ordered to emit extra heat to the
outdoor condenser. If also a swimming pool condenser is foreseen, he extra heat is diverted initially into the
swimming pool water, the residual heat will be diverted to the outdoor condenser.
COOLING PIPES
The distance between the dehumidifier and the outdoor condenser may be maximum 20 m.
The cooling pipes depend on the distance between dehumidifier and outdoor condenser and on the dehumidifier’s
capacity. Cooling pipes should be installed down to the outdoor condenser.
The installation of the cooling pipes must be made according to the rules of the art and must comply with the
standards. By preference to be done by a refrigerating installer.
Minimum dimensions cooling pipes:
Type of unit
65
92M-100
140-142M
Pressure pipe
3/8 “
3/8 “
½ “
Liquid pipe
3/8 “
3/8 “
3/8 “