Installation
3
AXP-CCS/AXM-CCS Softwire Camera Center
Installation
The AXP-CCS and AXM-CCS contain an AXP-AI8 Analog 8-Input Board and MSP Mini-
Softwire Panel that act as two AXlink devices. The factory-default setting for the AXP-AI8 is 129.
The MSP addresses for the AXP-CCS and AXM-CCS are 130 and 131 respectively.
Setting the AXlink Device Numbers
The AXlink device number range is 1 - 255. You must use two unique AXlink device numbers for
the AXP-AI8 and MSP to be recognized by the Axcess Control System. To set the AXlink device
numbers:
1.
Remove the four Phillips-head screws from the panel.
2.
Gently rotate the rear panel backward until you can lay it down flat to expose the AXP-AI8 and
MSP circuit cards. Locate the AXlink device DIP switch on the AXP-AI8 circuit card (FIG. 1)
and the MSP (FIG. 2).
3.
Set the AXlink device number on both the AXP-AI8 and MSP by setting DIP switch positions
1-8. The total value of all ON (up) positions on the DIP switch sets the device number. The
AXlink DIP switch example shown in the following table is set to 129 (factory default). The
device number takes effect only on power-up.
FIG. 1
AXP-AI8 AXlink device DIP switch location
FIG. 2
MSP circuit card and AXlink device DIP switch location
DIP Switch Positions and Values
Position
1
2
3
4
5
7
8
Value
1
2
4
8
16
64
128
AXlink device DIP switch
I/O DIP switch
20-pin Berg header ribbon
cable connector
1 2 3 4 5 6 7 8
AXlink device DIP switch
1 2 3 4 5 6 7 8
ON
Factory default
Summary of Contents for AXM-CCS
Page 1: ...instruction manual Camera Control Systems AXP CCS AXM CCS Softwire Camera Centers ...
Page 4: ...ii AXP CCS AXM CCS Softwire Camera Centers Table of Contents ...
Page 6: ...Product Information 2 AXP CCS AXM CCS Softwire Camera Centers ...
Page 13: ...Programming 9 AXP CCS AXM CCS Softwire Camera Centers ...