Upgrading Modero Firmware
121
VG-Series Modero Touch Panels
Upgrading Modero Firmware
Overview
Before beginning the Upgrade process:
Setup and configure your NetLinx Master. Refer to your particular NetLinx Master instruction
manual for detailed setup procedures.
Calibrate and prepare the communication pages on the Modero panel for use. Refer to the
Panel Calibration
section on page 91.
Refer to the NetLinx Studio version 2.x or higher Help file for more information on uploading
files via Ethernet.
Configure your panel for either direct connect or wireless communication. Refer to the
Configuring Communication
section on page 93 for more detailed information about Ethernet
or Wireless communication.
The process of updating firmware involves the use of a communicating NetLinx Master. The required
steps for updating firmware to a Modero panel are virtually identical to those necessary for updating Kit
files to a NetLinx Master (
except the target device is a panel instead of a Master
). Refer to either your
Master’s literature or Studio 2.x Help file for those procedures.
Upgrading the Modero Firmware via the USB port
Before beginning with this section, verify your panel is powered and the Type-A USB connector is
securely inserted into the PC’s USB port.
The panel must be powered-on before connecting the mini-
USB connector to the panel.
Step 1: Configure the panel for a USB Connection Type
1.
After the installation of the USB driver has been completed, confirm the proper installation of the
large Type-A USB connector to the PC's USB port, and restart your machine.
2.
After the panel powers-up, press and hold the grey Front Setup Access button (
for 3 seconds
) to
continue with the setup process and proceed to the Setup page.
3.
Select
Protected Setup
>
System Settings
(located on the lower-left) to open the System Settings
page.
4.
Toggle the blue
Type
field (
from the Master Connection section
) until the choice cycles to
USB
.
It is recommended that firmware KIT files only be transferred over a direct Ethernet
connection and only when the panel is connected to a power supply.
If battery power or wireless connection fails during a firmware upgrade, the panel
flash file system may become corrupted.
A touch panel which is not using a valid username and password will not be able to
communicate with a secured Master. If you are updating the firmware on or through a
panel which is not using a username or password field, you must first remove the
Master Security feature to establish an unsecured connection.
Establishing a USB connection between the PC and the panel, prior to installing the
latest NetLinx Studio and TPDesign4 applications will cause a failure in the USB
driver installation.
This driver must first be saved to the PC as part of the new NetLinx Studio and
TPDesign4 application installations.
Summary of Contents for Modero NXT-1500VG
Page 4: ......
Page 62: ...Touch Panel Accessories 52 VG Series Modero Touch Panels...
Page 100: ...Installation Procedures 17 Panels 90 VG Series Modero Touch Panels...
Page 178: ...Firmware Pages and Descriptions 168 VG Series Modero Touch Panels...
Page 250: ...Appendix 240 VG Series Modero Touch Panels...
Page 251: ...Appendix 241 7 Modero Widescreen Touch Panels...