KNX Connector

The KNX connector on the rear panel is a 2-pin captive-wire connector that 
provides communication between the NXB-KNX and the KNX control system 
via 2-wire shielded twisted pair cabling (FIG. 4). 

Configuration

NXB-KNX units have a built-in WebConsole that allows you to make various 
configuration settings via a web browser on any PC that has access to the 
Master. The web console consists of a series of web pages that are collectively 
called the "NXB-KNX Configuration Manager".

Determining the IP Address of the NXB-KNX

NXB-KNX units feature a built-in zero-configuration networking client that 
allows you to determine the unit’s IP address via Bonjour or a similar zero-
configuration client. Zeroconf (also known as "Bonjour") technology provides a 
general method to discover services on a local area network. In essence, it 
allows you to set up a network without any configuration, as described below.

Zero-Configuration (Bonjour) Client

You will need a zero-configuration client to determine the IP address of the 
NXB-KNX. There are many zero-configuration clients available. However, for 
the purposes of this document, we will refer to the Bonjour plugin for Internet 
Explorer. It is free and widely available for download. 

If you don’t already have it installed on your PC, download and install 

Bonjour 

for Windows

 before you begin. 

Note

: The NXB-KNX is set to 

DHCP

 by default. Bonjour requires DHCP to 

discover the device, so don’t change this setting until you have identified the 
unit on your network.

1.

With 

Bonjour for Windows

 running on a PC that has access to the LAN 

that the NXB-KNX resides on, connect the NXB-KNX to the network (see 
the 

Wiring and Connections

 section). 

2.

In Bonjour, you will see the unit join the network at power up. 

3.

In Bonjour, click on the NXB-KNX link and it will access the unit's 
Configuration Manager (IP Settings page).

4.

The unit’s IP Address is displayed in the 

IP Settings page

.

At this point you can assign a new IP Address if necessary.

Accessing the WebConsole

From any PC that has access to the LAN that the NXB-KNX resides on:

1.

Open a web browser and type the IP Address of the target NXB-KNX unit 
in the Address Bar. 

2.

Press Enter to access the WebConsole for the specified NXB-KNX unit. 
The initial view is the 

IP Settings

 page. 

Admin Menu

There are several configuration pages included in the Configuration Manager, 
all of which are accessed via the 

Admin

 drop-down menu (FIG. 5): 

Click on an option in this menu to access each of the configuration pages, as 
described in the following sub-sections:

Security Settings

Select 

Security Settings

 from the Admin drop-down menu to open the 

Security Settings

 page. Use the options on the page to specify security options 

and login information for this NXB-KNX unit. 

Enable / Disable Security Settings 

Login Information

Use this set of options to specify a Username and Password. These will be 
required only if one or more of the Security Settings are enabled. 

Click 

Accept

 to save your changes, changes on this page take effect 

immediately. 

Click 

Cancel

 to cancel any changes.

IP Settings

Select 

IP Settings

 from the Admin drop-down menu to open the 

IP Settings

 

page. Use the options on the page to specify network/IP settings for this 
NXB-KNX unit.    

Additional Documentation

Refer to the 

NXB-KNX Operation/Reference Guide

 (available to view/download 

at www.amx.com) for additional configuration information, including instructions 
on using the Clock Manager, Application and Firmware upgrades.

FIG. 4  

KNX Connector wiring diagram

FIG. 5  

NXB-KNX Configuration Manager -Admin menu

KNX

Control 

Bus

2-wire twisted pair

+

-

Web Security:

Click this checkbox to enable Web Security. 

When Web security is enabled, a username and password are 
required to access any system Web pages (default = 
disabled).

Telnet Security:

Click this checkbox to enable Telnet Security.

With Telnet Security enabled, a username and password are 
required to establish a Telnet or SSH connection 
(default = disabled).

Admin Security:

Click this checkbox to enable Admin Security.

With Admin Security enabled, a username and password are 
required to modify any system configuration item (default = 
disabled).

Restore Factory 
Defaults:

Click to restore all security settings to their factory default (all 
disabled).

Username:

Enter the Username that will be required to login to this unit 
id security is enabled.

New Password:

Enter a new password that will be required to login to this 
unit if security is enabled.

Confirm Password:

Re-enter the new password in this field.

Restore Factory 
Defaults:

Click to restore the login information to the factory defaults:

• Default Username = 

administrator

• Default Password = 

password

DHCP:

Click to toggle DHCP on this unit (default = enabled). 

Note

: DHCP must be enabled in order for the zero-configuration 

client (i.e. Bonjour for Windows) to detect the NXB-KNX on the 
network.

Hostname:

Enter a Hostname for this unit (enabled only if DHCP is 
disabled.

IP Address:

Enter an IP Address for this unit (enabled only if DHCP is 
disabled).

Subnet Mask:

Enter a Subnet Mask for this unit (enabled only if DHCP is 
disabled).

Gateway:

Enter a Gateway for this unit (enabled only if DHCP is disabled).

Domain Suffix:

Enter the Domain Suffix for this unit.

DNS 1, 2, 3:

Enter up to three DNS addresses for this unit.

Reboot:

Click to initiate a system reboot. IP Settings changes only take 
effect after a reboot.