Page 2 of 3 08/07/00 Rev. B 

6. Make sure the RJ-45 connectors have been correctly installed on the PHASTLink cables and 

insert the RJ-45 connectors in the RJ-45 jacks on the back of the PLL-SW10. Make sure the 
connectors are fully seated in the jacks. 

7. For optimum performance, we recommend the installation of a double 120-ohm terminator in 

one of the RJ-45 jacks of the last device (or the only device) in a chain of PHASTLink 
devices. To build a double 120-ohm terminator: 

a. Install a 120-ohm resistor between pins 1 and 2 of an RJ-45 connector. See Figure 4 for 

RJ-45 pin numbers. 

b. Install a 120-ohm resistor between pins 7 and 8 of the same RJ-45 connector. 

Note: Use ¼-watt or larger resistors. 

8. Make sure there is a minimum 0.25-inch gap between all high- and low-voltage components. 

9. Remove the plastic face plate and mount the PLL-SW10 in the junction box. 

10. Screw the PLL-SW10 to the junction box through the mounting slots. 

CAUTION! 

To avoid damaging this device and voiding the warranty: 

• 

DO NOT connect the ground wire (green) or the 3-way control wire (blue) to the hot, load, 
or neutral wires. 

• 

DO NOT short the load wire (red) to the ground, common, or 3-way control wires. 

 

 

 

 

 

 

 

 

 

Figure 2 - Wiring Diagram      Figure 3 - RJ-45 

Note: For multi-gang installations, break off the metal tabs on the four corners of the metal 

heat sink. The tabs on the outer-most devices may be left intact. Up to five PLL-SW10 
units can be mounted in one multi-gang junction box without de-rating the load capacity. 

 Troubleshooting 

Problem: LED does not come on at power-up. 

1. Check the voltage across the Hot and Common wires to make sure the device is getting 

power (should be 120VAC). 

2. Make sure the 3-way Control wire is not shorted to Ground. If this wire is shorted, the device 

may appear in Landmark Designer, but it will not operate via the button. 

 

Problem: Device works, but does not appear in Landmark Designer. 

1. Check the PHASTLink cable. 

1 2 3 4 5 6 7 8

RJ-45 

PHASTLink 

Neutral 