background image

 

 

4

the case, you can increase the output voltage of the unit that is reading low using the output adjust 
potentiometer. 
 

OPERATION 

 
Turn the switch on the top of the unit on to energize the outputs.  The green ‘Output On’ indicator 
light will glow to indicate the proper operation of the unit. 
 

OUTPUT ADJUSTMENT 

 
The unit has an adjustment potentiometer to allow up to 

±

 0.5V adjustment of the output voltage.  

This potentiometer is accessed through a small hole in the top of the power supply.  As shipped from 
the factory, the unit is preset for a voltage of 13.6, 27.2 or 54.4VDC.  If you wish to adjust this 
voltage, remove the cover plate (secured by 2 screws) to expose the Output Adjust potentiometer.  
Reach in with a very small flat blade screwdriver to rotate the potentiometer.  Clockwise increases the 
output voltage and counter clockwise decreases it.  When you are done, replace the cover plate and 
securely tighten the screws. 
 

METERS 

 
1 or 2 high quality 2 ½ inch analog meters can be added to the charger (factory installed only).  1 
ammeter allows monitoring of total output current.  2 ammeters allow independant monitoring of the 
current into each of the output terminals.  1 ammeter and 1 voltmeter allow monitoring of total output 
current and output voltage. 

 

TROUBLE SHOOTING 

 

This unit provides LED indicators and a buzzer to help diagnose any problems.  The unit should 
sound the buzzer to alert you prior to shutting itself down.  You should immediately check the 
indicators to determine the cause of the shutdown. 
 

• 

LOW OUTPUT 

Indicates that the output voltage is below normal because: 

• 

The current demanded by the devices connected to the unit exceeds the 
maximum output current rating, thereby causing the output voltage to drop 
to maintain the current at the maximum level, 

• 

The input voltage is not high enough for unit to operate, 

 

• 

LOW INPUT 

Indicates that the input voltage is below normal because: 

• 

The input voltage is not in the correct range for proper operation of the unit. 

 

• 

OVERHEAT 

Indicates that the power supply is running too hot because: 

• 

Too much power is being drawn, turn off or unplug some devices. 

• 

The power supply is located in a poorly ventilated area. 

 
If the load exceeds the continuous rating for too long a period, the temperature sensor inside the unit 
will turn off the outputs.  After the unit cools sufficiently, it will automatically come back on.  If this 
happens frequently, remount the unit for increased airflow so it cools better. 

Summary of Contents for PWS610 Series

Page 1: ...PWS610 Series Power Supply Installation Operation Manual ...

Page 2: ...and ordinances DANGER Never alter AC cord or plug provided if it will not fit outlet have proper cord installed by a qualified electrician Improper connection can result in a risk of an electric shock Analytic Systems does not recommend the use of the PWS610 Series Power Supplies in life support applications where failure or malfunction of this product can be reasonably expected to cause failure o...

Page 3: ... Input Fuse MDA 12 6 Output Voltages Nominal op 12Vdc 24Vdc 48Vdc Actual 13 6 0 05Vdc 27 2 0 05Vdc 54 4 0 10Vdc Adjust 0 5 Output Crowbar 16 0 0 5 Vdc 32 0 1 0 Vdc 63 9 2 0 Vdc Output Amps cont 40 20 10 Output Amps max 45 25 12 5 Transient Response 1 V for 30A 1 V for 20A 1 V for 9 5A General Input Frequency 45 65 Hz Noise on Input 50 milli Volts Noise on Output 50 milli Volts Efficiency 80 maximu...

Page 4: ...ovided Connect only one wire to each terminal Ensure that the total average load connected does not exceed the continuous current rating of the unit LOAD SHARE OPTION The units may be configured for load sharing if they are equiped with the optional output isolation diodes To confirm that your unit has these diodes use an ohmmeter to measure the resistance between the two positive output terminals...

Page 5: ...current into each of the output terminals 1 ammeter and 1 voltmeter allow monitoring of total output current and output voltage TROUBLE SHOOTING This unit provides LED indicators and a buzzer to help diagnose any problems The unit should sound the buzzer to alert you prior to shutting itself down You should immediately check the indicators to determine the cause of the shutdown LOW OUTPUT Indicate...

Page 6: ... off the unit and move the jumper to the other position on J22 J22 is located next to the relay To change the position of the jumper first turn the unit off and disconnect the unit from both the power and batteries Next turn the unit on for 30 seconds to discharge the capacitors then turn it off again Turn the unit upside down and remove the four screws Remove the cover and locate J22 It will be n...

Page 7: ...OL A remote control panel may be connected to the power supply using a 9 pin D connector that attaches to the side of the power supply The remote control panel and D connector are part of the remote control option The remote control panel allows the unit to be operated remotely as well as duplicating all the diagnostic indicators and audible alarm ...

Page 8: ...o remedy the defect after having a reasonable number of opportunities to do so 5 Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by anyone else shall render this warranty void 6 There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misuse of the equipment including exposure to excessive heat salt or fresh wate...

Reviews: