Power Wiring
ANCA Motion
D-000088 Rev 09
43
6
Recommended AC Circuit Breakers and Supply Wire Sizes
Drive Type
Current
Rating (nom.)
AC Supply
Input Current
(max. A rms)
Circuit Breaker
Rating (C-type)
Ø Wire Gauge (min.)
AWG
mm
2
AMD2103
3 A
1Φ power
5 A
6 A
16
1.5
3Φ power
5 A
6 A
16
1.5
1Φ control
0.5 A
2 A
20
0.5
AMD2109
9 A
1Φ power
13 A
16 A
14
2.5
3Φ power
13 A
16 A
14
2.5
1Φ control
0.5 A
2 A
20
0.5
AMD2015
15 A
1Φ power
13 A
16 A
14
2.5
3Φ power
13 A
16 A
14
2.5
1Φ control
0.5 A
2 A
20
0.5
Recommended DC Circuit Breakers and Supply Wire Sizes
Drive Type
Current
Rating (nom.)
DC Supply
Input Current
(max. DCA)
Circuit Breaker
Rating (C-type)
Ø Wire Gauge (min.)
AWG
mm
2
AMD2103
3 A
Power
3 A
4 A
16
1.5
Control
0.5 A
1 A
20
0.5
AMD2109
9 A
1Φ power
9 A
10 A
14
2.5
3Φ power
13.8 A
16 A
14
2.5
1Φ control
0.5 A
2 A
20
0.5
AMD2015
15 A
1Φ power
9 A
10 A
14
2.5
3Φ power
13.8 A
16 A
14
2.5
1Φ control
0.5 A
2 A
20
0.5
Note: All wire sizes are based on 75 °C (167 °F) copper wire. Use of higher temperature cable may allow
smaller gauge wires. Size cables to conform to the local electrical installation regulations.
The mains supply wire should be used for the following power connections:
AC supply to external EMC filter
AC supply (or external EMC filter) to drive
Cable sizes are a guidance only as installation methods such as grouping, length, use of conduits and
ambient temperature may affect current capacity
Where more than one cable per terminal is used the combined diameters should not exceed the
maximum.
The terminals are suitable for both solid and stranded wires.
Circuit Breakers must be thermal magnetic type.
Motor cables should have the same wire gauge as 3 phase mains supply.
Summary of Contents for AMD2000 Series
Page 1: ...AMD2000 Series D2xxx Servo Drive User Guide D 000088 Rev 10 ...
Page 131: ...Technical Data ANCA Motion D 000088 Rev 09 119 10 ...
Page 132: ...AMD2000 Series D2xxx Servo Drive User Guide 120 D 000088 Rev 10 ANCA Motion 10 9 1 2 3 Phase ...
Page 133: ...Technical Data ANCA Motion D 000088 Rev 09 121 10 ...
Page 135: ...Technical Data ANCA Motion D 000088 Rev 09 123 10 ...
Page 136: ...AMD2000 Series D2xxx Servo Drive User Guide 124 D 000088 Rev 10 ANCA Motion 10 9 2 2 3 Phase ...
Page 137: ...Technical Data ANCA Motion D 000088 Rev 09 125 10 ...
Page 139: ...Technical Data ANCA Motion D 000088 Rev 09 127 10 ...
Page 140: ...AMD2000 Series D2xxx Servo Drive User Guide 128 D 000088 Rev 10 ANCA Motion ...
Page 141: ...Technical Data ANCA Motion D 000088 Rev 09 129 10 10 9 3 2 3 Phase ...
Page 142: ...AMD2000 Series D2xxx Servo Drive User Guide 130 D 000088 Rev 10 ANCA Motion ...