ANC Technology

18

If no sound is heard from the valve, check if the cable from the valve controller has
been cut or broken. Check the connector in the extension tube, make sure it is clean,
dry and the retaining nut is tightened.
1. Verify continuity of the valve solenoid with an ohmmeter, 2 to 6 ohms resistance
is typical.
2. If a sound is heard from the valve, and water does not flow, make sure the water
inlet has pressure.
3. If a sound is heard form the valve, the valve may be stuck, remove the valve and
check for an obstruction, if nothing is found, replace the valve.
4. If no click is heard from the controller, make sure the battery is charged. The
main controller shows the battery charge. If the battery charge is OK, replace the
controller. If the battery charge is low, and the solar exposure has been normal,
replace the battery.

2.

Q: Why after learning a new current wet level, does the system not stop irrigating

right away?
A: Possibly one of the following:

A: If the moisture sensor is moved after learning the wet level, it may be incorrect.
Should redo the learning process.
B: If water is manually added to the soil, then a wet level is learned; the learned
level could be very high, since water could be temporarily accumulated on the
surface. Use the displayed % reading as a guide to determine what reading is correct.
If the learned value is too high, learn the moisture level again later when the soil
dries to the desired level.
C: The LED “Irrigating” is off, but still the system is still irrigating. See FAQ 1,

about valve problems.

D: On the main controller show this zone is irrigation, but has no problems as

described at A and B. then maybe it is sensor problem, please reference questions.

3

. Q: How to determine if the moisture sensor is working normally?

Summary of Contents for 1MS1V-Solar

Page 1: ...1 1 Moisture 1 Valve Wireless Field Irrigation Controller 1MS1V Solar User Manual 2014 ANC Technology www anctech com REV 1 03...

Page 2: ...VALVES 9 9 SYSTEM SETUP 10 9 1 HOW TO INSTALL PRESSURE SWITCH PRESSURE METER 10 9 2 ENABLE PRESSURE SWITCH METER 13 9 3 PRESSURE CHECK DELAY 13 9 4 VALVE DRIVE LEVEL SETUP 13 9 5 ADJUST DRY WET CONTRO...

Page 3: ...20mA 3 8W Back up battery 10 1 2V 2 3AH AA Size Quiescent current 1mA Frequency 902 928 MHZ Communication distance at open space 1600ft Working environment Temperature 30 60 Humidity 90 Duration of fu...

Page 4: ...0 06Mpa 0 6Mpa 0 1Mpa 1 3Mpa 2 Threads Optional 1 4 NPT or 1 4G 3 Extension cable is up to 50 meters Pressure Meter 1 Range 0 1 1 0 Mpa 2 Accuracy 1 3 Outport 4 20mA 4 Supply power 9 15VDC 5 Thread O...

Page 5: ...attery 1 Battery specification Rechargeable Ni MH AA battery 1 2v 10 2 Suggest to use rechargeable battery with more than 2300mAh Battery box cover 3 Take out battery box put Ni MH AA rechargeable bat...

Page 6: ...After power on the controller will start to do the following check 1 Check battery voltage If the voltage is lower than working voltage the controller will turn selves off and wait until the battery i...

Page 7: ...te to reach main controller During searching time keys been locked LCD shows Searching Comm path After route is been established there will be two beeps the controller is ready for work If failed to e...

Page 8: ...ller the relay route could be 1 2 or 3 layers Field controllers will report route to the main controller the main controller will save this information and follow this route to communicate with field...

Page 9: ...e has Manual Auto Manual Auto loop operation Also can manually open close valve by using Remoter Romoter 1 for the convenience of mainterance If user did manual open close the valve will keep open clo...

Page 10: ...nu key into system setup menu push or Browse Menu keys to browse there are three sub menus Set up sensor Set up valve User help Push Enter Save key into the menu push Exit Delete key to exit the syste...

Page 11: ...t the water pressure from the valve Note a Make sure the 3 way connector thread match with pipe and water pressure switch meter b The water proof protection wrap of the pressure switch meter needs to...

Page 12: ...On FAILURE check if the water pressure meets the min requirement Pressure meter doesn t need adjusting f If the valve been closed normally but shows OFF FAILURE on LCD do same as above but turn the sc...

Page 13: ...essure check delay Water pressure takes time to establish so there must have a time delay to check the water pressure to avoid misalarm Out of factory default is 1 minute user can adjust up to 99 minu...

Page 14: ...gher than Dry Control Level 9 6 Register this device with main controller Register with main controller will establish bidirectional wireless communication channel with main controller Register and de...

Page 15: ...u Now push Browse Menu key to choose Register Remove and push Enter Save key to begin register or remove Moisture Sensor After the wireless field controller into registering status let the main contro...

Page 16: ...ew one from ANC Technology or send one old version field controller to ANC Technology for update at a fee This new version field controller would be used to update all other existing wireless field co...

Page 17: ...en the LCD does not show Irrigating the irrigation is on A Possibly one of the following A For user wired valves at the time of installation check the magnetic valve connection polarity most probably...

Page 18: ...he solar exposure has been normal replace the battery 2 Q Why after learning a new current wet level does the system not stop irrigating right away A Possibly one of the following A If the moisture se...

Page 19: ...Q When using several wireless field controllers why is there so little water flow A Possibly one of the following A Check and see if the Maximum number of simultaneously irrigated zones is too many C...

Page 20: ...broken or magnetic valve has problem If the senor is buried deep this could be normal and ignored Screen will display the error and system will beep to remind the user to take a look at the field One...

Page 21: ...se valve failure and accompanies long time beep Q When the main controller or wireless field controller turn on off valves it will check if the valve open close normal or not if the pressure switch de...

Page 22: ...pping to ANC ANC pays shipping to customer 6 Beyond the warranty period or for damage caused by customer or for other than defects in material or workmanship ANC offers repair service at customer s ex...

Reviews: