26
water level, will protectively turn off the pump.
Note
:
Sensor which is not been installed, make sure not been chosen in the protection setup.
Otherwise the pump can’t operate normal.
6.3.3 Setup pump protective time delay
Browse into“Safety detection delay”menu, LCD show current setup as following:
Set up range is
1-
99 minutes.
This duration time is time need from start of the pump until flow rate and water pressure is
been stabilized. If time delay too short, will produce faulty protective shut down of the pump,
too long, will lost some meaning of protection. Needs to observe and adjusting the setup
until right.
6.4 How to setup master valve
Browse into“
Set up master valve
” menu
,
there are Reg/remove master valve, Detection
sensor options, and On/off detection delay 3 choices as following:
6.4.1 Register/Remove master valve
Reference 6.1.1 flow meter registration and remove.