[ USER ENTERED TEXT ]
ñ
NOTE: Refer to General Instrument Operation - Modifying Text
for information on this operation.
Definition: This text parameter defines the CPRC Input Tag that is
shown on the user display.
ÿø
TO ADVANCE TO NEXT SELECTION
CPRC INP DECIMAL POS
X
ÿü
to change,
õö
to choose,
ÿþ
to save
Definition: This parameter selects active decimal places for the CPRC
user display.
ÿø
TO ADVANCE TO NEXT SELECTION
CPRC INP RANGE LOW
X
ñ
NOTE: Not shown if input type RTD.
Definition: This parameter selects low input range for the CPRC input.
Typical setting is 4.00 mA. MUST match output of
sensor.
ÿø
TO ADVANCE TO NEXT SELECTION
CPRC INP RANGE HIGH
X
ñ
NOTE: Not shown if input type RTD.
Definition: This parameter selects high input range for the CPRC
input. Typical setting is 20.00 mA. MUST match output
of sensor.
Revision 3.0
Section 7
15