ANDREWS COMBIfl o
44
GB
5.2 COMMISSIONING THE HEAT ENGINES
5.2.1 IMPORTANT NOTES
WARNING
The gas mixture and burner off -set gas rate (minimum load rate) is preset by the manufacturer.
Please
DO NOT
attempt to change the settings of the off -set governor behind the sealed cover.
CAUTION
It is an essential part of commissioning process to check the full load gas rate of the appliance and
the combustion emission levels are correct.
The heat engines on this appliance have been set by the manufacturer, but this will need to
be checked again when the appliance has been fully installed into its operating environment.
The commissioning process involves the operation of the individual heat engines at the
maximum possible heat load. As this appliance contains several heat engines, the manufacturer
recommends that commissioning is carried out using Siemens OCI700 service tool or the Andrews
commissioning tool, available directly from the manufacturer. If neither of these tools are available
to the commissioning agent, then the following manual procedure can be used:-
5.2.2 HEAT ENGINE ONE (TOP MOST UNIT) COMMISSIONING
Ensure that all the numbered points included in section 5.1 “Commissioning General” have been completed
successfully before proceeding with the following:-
1. Remove the fl ue sample point bung from the fl ue duct pipe (see illustration below)
Flue sample point
2. Insert a calibrated combustion analyser (approx 65mm) inside the fl ue sample point
3. Ensure that the DHW tank temperature is below 40
O
C. Drawer off water until the tank temperature is
below this value. The temperature can be checked on the home page of the appliance display (see
below)
Home page
DHW temperature
Cascade fl ow temp
72.3
o
C
DHW temp 1
42.3
o
C
Outside temp
16.0
o
C
Water pressure
1.2bar
Off -set governor cover
DO NOT REMOVE
DO NOT ADJUST
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...