Code Fault Description
Sub
Code
Notes
142
Device failure (Bus)
Any
Check that the heater and OZW672 is powered and connected cor-
rectly.
151
BMU Internal error
330
331
Ignition output error. Check operation of spark generator. Replace PCB
is fault if no fault with the spark generator is found.
332
333
Gas valve output error. Check operation of gas valve (neon indicator).
Replace PCB if no fault with the gas valve found.
Other
Check if polarity of live and neutral has been reversed to the appliance.
Replace PCB if fault repeatedly occurs.
152
Parameterization error
Any
Incorrect / confl icting parameters input (last changed parameters need
to be investigated).
153
Unit Locked
622
Check condense line for blockage / Reset button pressed too long
(>10s).
848
849
Parameter update fi nished. Press reset to apply changes.
160
Fan speed threshold not reached Any
Fan does not reach required speed setpoint via PWM control- Check
wiring and operation of fan. Replace fan if necessary
377
Fan speed not reached - Home run stage
378
Fan speed not reached - Standby stage
379
Fan speed not reached - Ignition stage
380
Fan speed not reached - Pre purge stage
381
Fan speed not reached - Post purge stage
171
Fault input 1
Any
User defi ned OZW672 input D1 has been activated.
172
Fault input 2
Any
User defi ned OZW672 input D2 has been activated.
183
Unit in parameterisation mode
Any
Code will be displayed when a programming stick is used but should
clear when programming is complete. Repeat stick operation if fault
code persists
217
Sensor error
Any
Ionisation current fault. Check operation of ionisation probe using pa-
rameter 8329 (menu - Diagnostics heat generation).
765
766
Short circuit of ionisation probe
218
Pressure supervision
Any
Water pressure inside boiler is low but not yet critical. Boiler will con-
tinue to operate but at 80% of maximum output. Full output power will
not be available until the water pressure is at or above 1.0 bar.
317
Mains frequency outside permit-
ted range
Any
Check electrical supply to heater.
320
DHW Charging temperature,
sensor error
Any
Check connections and / or replace faulty sensor (B36)
322
Water press 3 too high
Any
Water pressure inside the boiler is too high for safe operation. Opera-
tion will automatically resume once water pressure is at or below maxi-
mum levels. Check that the boiler fl ow is not restricted or blocked.
323
Water press 3 too low
Any
Water pressure inside boiler is too low for safe operation. Operation will
automatically resume once water pressure is at or above minimum lev-
els. Increase water pressure by adding water to system, as necessary
324
Input BX, same sensors
Any
BX sensor duplicated - check parameters
325
Input BX/extension module,
same sensors
Any
BX extension module sensor duplicated - check parameters
327
Extension module, same function Any
Extension Modules duplicated - check parameters
6.6 FAULT CODES LIST (CONTINUED)
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...