Neutralisation
General
Neutralisation systems
Standard neutralisation system (DN)
Neutralisation system with pump (HN)
14
General
Condensate, created by the R600,
should be drained into the public drai-
ning system. The condensate PH is
between 3.0 and 3.5. National and/or
local regulations have to be checked, in
order to find out whether the condensa-
te should be neutralised before entering
the public draining system.
Type
DN2
DN3
Applicable for
[kW]
450
1500
Length [mm]
420
640
Width [mm]
300
400
Height [mm]
240
240
Type
HN1.5
HN2.5
Applicable for
[kW]
280
540
Length [mm]
410
640
Width [mm]
300
400
Height [mm]
290
240
Power con-
sumption pump
[W] 40 150
Pump head
[m]
6
3
Neutralisation systems
The neutralisation systems can be pla-
ced in the bottom section of the boiler.
The delivery of the system contains the
following components:
•
Granulate for first filling
•
Connection hoses for inlet and outlet
connection
•
Boiler connection adapter
For the neutralisation two different sys-
tems are available:
Standard neutralisation system (DN)
The standard neutrlisation system is used, when the public draining connection is
at lower level than the boiler syphon connection.
Neutralisation system with pump (HN)
The neutralisation system with pump is used, when the public draining system is at higher level than the boiler syphon con-
nection and the condensate needs to be transported to a higher level before draining is possible. The built-in pump of the
neutralisation system takes care of the transport of the condensate.
The maximum amount of condensate
for each boiler type can be found in the
chapter „Technical data“.