29
Set S: LOGON B
The R600 can be extended with a LO-
GON B controller for extended control
of two heating zones and sanitary hot
water operation. The LOGON B combi-
nes weather compensated operation
with control of two heating zones and
the control of a secundary hot water
circulation pump.
The kit contains a LOGON B weather
compensated controller including con-
nection material for assembly into the
control panel of a R600 (standard versi-
on) and an outside temperature sensor.
1
2
3
5
4
6a
7a
6b 7b
6c 7c
8
9
1 KM628 (integrated in boiler)
2 Outside temperature sensor, to be connected at plug AF, terminals M-B9
3 LOGON B (integrated in boiler)
4 Primary sanitary hot water pump control, to be connected at plug BW, terminals N-PE-Q3
5 Sanitary hot water sensor, to be connected at plug BWF, terminals M-B3
6 Heating zone 1
a Temperature sensor, to be connected at plug VF1, terminals M-B1
b Pump, to be connected at plug HK1, terminals N-PE-Q2
c Mixing valve, to be connected at plug MISCHER1, terminals Y1-N-PE-Y2
7 Heating zone 2
a Temperature sensor, to be connected at plug VF2, terminals M-B12
b Pump, to be connected at plug HK2, terminals N-PE-Q6
c Mixing valve, to be connected at plug MISCHER2, terminals Y5-N-PE-Y6
8 Sanitary hot water circulation pump, to be connected at plug MFA3, terminals N-PE-QX3
9 Header sensor, to be connected at plug MFF2, terminals M-BX2
Further details about the electrical connections can be found on the wiring diagram.